CRHS - Building, Mechanical, Electrical and other Condition Reports

AuthorityDepartment of Infrastructure
Date received2021-06-16
OutcomeUpheld - partial
Outcome date2021-10-19
Case ID1849793

Summary

The request sought specific building, mechanical, and electrical condition reports for the CRHS business case and subsequent ad hoc reports, along with methodology details for monitoring the education estate. The Department of Infrastructure partially upheld the request, disclosing a December 2016 Suitability Study that assessed room conditions, accessibility, and infrastructure against current legislation.

Key Facts

  • The disclosed document is a Suitability Study from December 2016 intended to inform the business case for replacing the existing school.
  • The study evaluates principal spaces based on their impact on teaching, health and safety, security, and disabled access.
  • Multiple rooms were flagged for having door widths narrower than required by current legislation for wheelchair access.
  • Specific issues identified include lack of natural ventilation, inadequate heating, and insufficient ICT infrastructure in various offices and staff areas.
  • The methodology for the study is referenced as being attached in Appendix 1 of the report.

Data Disclosed

  • December 2016
  • 2017
  • 2018
  • 2021-06-16
  • 2021-10-19
  • Room Ref A103
  • Room Ref A105
  • Room Ref A106
  • Room Ref A107
  • Room Ref A108
  • Room Ref A109
  • Room Ref A110
  • Room Ref A111
  • Room Ref A112
  • Room Ref A113
  • Room Ref A114
  • Room Ref A115
  • Room Ref A116
  • 299 pages
  • 8 documents

Original Request

Further to an oral question (No.14) in the House of Keys (12th June 2018 sitting) an email was sent on behalf of the then DESC Minister to 'Mr President, Mr Speaker and Honourable Members.' This e-mail is a matter of public record viz: https://www.tynwald.org.im/business/hansard/20002020/k180612-HA-Q1.14.pdf The final paragraph of this e-mail states: 'I understand updated condition reports have not yet been undertaken across the Education estate by the DOI, but rather specific ad hoc condition reports into specific issues when required. Certainly for the new CRHS business case in 2017, DOI at our behest undertook specific reports on the building, and mechanical and electrical condition. It was thought then that the method used then, including condition scoring, could form a suitable basis for rolling out further surveys across the Education estate.' I seek the specific reports referred to by the Minister relating to the new CRHS business case together with such additional condition reports covering any area for CRHS (ad hoc or otherwise) compiled since the 'business case' reports were completed. To accompany this information it would be appreciated by way of help and advice if the Department could provide detail of the methodology/periodicity of how it monitors, assesses and conducts improvements to the material condition of the Island's primary and secondary school education estate.

Data Tables (161)

Spaces Direct Impact on Education H & S/ Security Disabled Access Comments
Typ Category
loohcS mooR feR tessA mooR edoC epahS/eziS tnemnorivnE noitacoL erutinruF dexiF erutcurtsarfnI TCI A B C D hgiH muideM woL seY oN
Admin corridor A103 0
0
0
0
0
Storage of items awaiting pickup due to lack of storage.
Doors off to accommodation are narrower than required by current legislation.
General office A105 1 Awkward shape for furniture layout.
1 Cold in winter as door to reception is open due to restricted layout.
0
0
1 Lack of data and power sockets.
Storage of items awaiting pickup due to lack of storage.
Access doors are narrower than required by current legislation.
Office A106 0
2 No direct daylight or natural ventilation.
0
0
0
Electronic door lock due to storage of sensitive information.
Access doors are narrower than required by current legislation.
Spaces Direct Impact on Education H & S/ Security Disabled Access Comments
Typ Category
loohcS mooR feR tessA mooR edoC epahS/eziS tnemnorivnE noitacoL erutinruF dexiF erutcurtsarfnI TCI A B C D hgiH muideM woL seY oN
Male staff toilet A107 0
0
0
0
0
Disabled toilet provision adjacent.
Photo copier A108 1 Small room with inadequate space for materials and personnel.
1 Minimal mechanical ventilation. Hot in summer.
0
0
0
Congested space.
Access door is narrower than required by current legislation. No space to manoeuvre.
Store A109 0
0
0
0
0
Narrow door width does not comply with current requirements for wheelchair access.
Spaces Direct Impact on Education H & S/ Security Disabled Access Comments
Typ Category
loohcS mooR feR tessA mooR edoC epahS/eziS tnemnorivnE noitacoL erutinruF dexiF erutcurtsarfnI TCI A B C D hgiH muideM woL seY oN
Office A110 0
0
0
0
0
Narrow door width does not comply with current requirements for wheelchair access.
Female staff toilet A111 0
0
0
0
0
Disabled toilet adjacent.
Deputy Head’s office A112 0
0
0
0
0
Narrow door width does not comply with current requirements for wheelchair access.
Spaces Direct Impact on Education H & S/ Security Disabled Access Comments
Typ Category
loohcS mooR feR tessA mooR edoC epahS/eziS tnemnorivnE noitacoL erutinruF dexiF erutcurtsarfnI TCI A B C D hgiH muideM woL seY oN
Disabled toilet A113 0
0
0
0
0
Narrow door width does not comply with current requirements for wheelchair access.
Deputy Head’s office A114 0
0
0
0
0
Narrow door width does not comply with current requirements for wheelchair access.
Head Teacher’s office A115 1 Room’s poor shape limits furniture layout options.
0
0
0
0
Narrow door width does not comply with current requirements for wheelchair access.
Spaces Direct Impact on Education H & S/ Security Disabled Access Comments
Typ Category
loohcS mooR feR tessA mooR edoC epahS/eziS tnemnorivnE noitacoL erutinruF dexiF erutcurtsarfnI TCI A B C D hgiH muideM woL seY oN
Office A116 0
1 Area generally lacking heating.
2 No disabled access from main school accommodation.
0
0
Access door is narrower than required by current legislation. Access for wheelchair bound person requires them to exit the school and re-enter adjacent to this room due to stairs in corridor from admin area
Corridor A119 0
0
2 No disabled access from main school accommodation.
0
0
No disabled access from within main school building.
Office Listening A120 0
0
2 No disabled access from main school accommodation.
0
0
Narrow door width does not comply with current requirements for wheelchair access.
Spaces Direct Impact on Education H & S/ Security Disabled Access Comments
Typ Category
loohcS mooR feR tessA mooR edoC epahS/eziS tnemnorivnE noitacoL erutinruF dexiF erutcurtsarfnI TCI A B C D hgiH muideM woL seY oN
Toilet A122 0
0
0
0
0
No disabled toilet provision on this level.
Medical room A124 0
1 Area generally lacking heating.
2 No disabled access to medical room without having to exit the main building and re-enter.
0
0
Access door is narrower than required by current legislation. Access for wheelchair bound person requires them to exit the school and re-enter adjacent to this room due to stairs in corridor from admin area.
Corridor A125 0
0
0
0
0
Spaces Direct Impact on Education H & S/ Security Disabled Access Comments
Typ Category
loohcS mooR feR tessA mooR edoC epahS/eziS tnemnorivnE noitacoL erutinruF dexiF erutcurtsarfnI TCI A B C D hgiH muideM woL seY oN
Staffroom A127 1 Not sufficiently large to comfortably allow full staff meetings.
0
1 Remote from remainder of school. Not heavily utilised.
0
1 Lack of data and power outlets.
Narrow door width does not comply with current requirements for wheelchair access.
Stair A125 0
0
0
0
0
No disabled access to the upper floor meeting rooms.
Kitchen A461 0
0
0
0
0
Narrow door width does not comply with current requirements for wheelchair access.
Spaces Direct Impact on Education H & S/ Security Disabled Access Comments
Typ Category
loohcS mooR feR tessA mooR edoC epahS/eziS tnemnorivnE noitacoL erutinruF dexiF erutcurtsarfnI TCI A B C D hgiH muideM woL seY oN
Conference room A462a 0
?
2 No disabled access to this level.
0
?
No disabled access to this level.
Meeting room A426 0
?
2 No disabled access to this level.
0
?
No disabled access to this level.
Spaces Direct Impact on Education H & S/ Security Disabled Access Comments
Type Category
euqinU mooR feR noitangiseD mooR edoC epahS/eziS tnemnorivnE noitacoL erutinruF dexiF erutcurtsarfnI TCI A B C D hgiH muideM woL seY oN
Class 3 R161 2 Room size well below recommended standard class area (BB98)
0
0
2 Student lockers in classroom, reduce space, access difficulties, lack of use.
0
Lockers access and lack of space for disabled
Narrow door does not comply with current requirements.
Class 4 R163 1 Room area marginal.
0
0
2 Student lockers in classroom, reduce space, access difficulties, lack of use.
0
Lockers access and lack of space for disabled
Narrow door does not comply with current requirements.
Office 5 R167 0
0
0
0
0
Narrow door does not comply with current requirements.
Spaces Direct Impact on Education H & S/ Security Disabled Access Comments
Type Category
euqinU mooR feR noitangiseD mooR edoC epahS/eziS tnemnorivnE noitacoL erutinruF dexiF erutcurtsarfnI TCI A B C D hgiH muideM woL seY oN
Class 6 R181 2 Room size well below recommended standard class area (BB98)
0
0
2 Student lockers in classroom, reduce space, access difficulties, lack of use.
0
Lockers access and lack of space for disabled
Narrow door does not comply with current requirements.
Class 7 R183 1 Room area marginal.
0
0
2 Student lockers in classroom, reduce space, access difficulties, lack of use.
0
Lockers access and lack of space for disabled
Narrow door does not comply with current requirements.
Spaces Direct Impact on Education H & S/ Security Disabled Access Comments
Type Category
euqinU mooR feR noitangiseD mooR edoC epahS/eziS tnemnorivnE noitacoL erutinruF dexiF erutcurtsarfnI TCI A B C D hgiH muideM woL seY oN
Lab 1 L405 0/1 Room area marginal.
1 No blackout provision limits experiments. Mechanical vent.
2 At extreme end of ‘string’ of science labs, poor relationship to resources and Science staff facilities. Lack of prep room.
1 Fixed furniture layout restricts flexibility and supervision. Fume cupboards against wall limits visibility of experiments by students.
0 WIFI enabled
Single means of escape from room
Narrow door does not meet current requirements. Access by way of poor quality lift opening directly into Lab 2
Lan 1x L407 0/1 Small group room.
0
2 At extreme end of ‘string’ of science labs, poor relationship to resources and Science staff facilities.
0
0 WIFI enabled
Single means of escape from room if used for experiments.
Narrow door does not meet current requirements. Access by way of poor quality lift opening directly into Lab 2
Spaces Direct Impact on Education H & S/ Security Disabled Access Comments
Type Category
feR euqinU mooR noitangiseD mooR edoC epahS/eziS tnemnorivnE noitacoL erutinruF dexiF erutcurtsarfnI TCI A B C D hgiH muideM woL seY oN
Lab 2 L406 0/1 Room area marginal.
1 No blackout provision limits experiments. No mechanical vent.
1 Poor relationship to Science staff facilities.
1 Fixed furniture layout restricts flexibility and supervision. Fume cupboards against wall limits visibility of experiments by students.
0 WIFI enabled
Ramped floor at main access to lab. Second escape through chemical store/prep room.
Access by way of poor quality lift opening directly into Lab 2
Lab 2x L404 0/1 Small group room set up as computer room.
1 Poor ventilation
1 Poor relationship to Science staff facilities.
0
0
Narrow door does not meet current requirements. Access by way of poor quality lift opening directly into Lab 2
Prep 2/3 L408 0
1 Poor ventilation
0
0
0
Lab 3 and 4 second means of escape is through the prep area, potentially impeded by furniture and equipment.
Narrow door does not meet current requirements. Access by way of poor quality lift opening directly into Lab 2
Spaces Direct Impact on Education H & S/ Security Disabled Access Comments
Type Category
feR euqinU mooR noitangiseD mooR edoC epahS/eziS tnemnorivnE noitacoL erutinruF dexiF erutcurtsarfnI TCI A B C D hgiH muideM woL seY oN
Lab 3 L410 0/1 Room area marginal.
1 No blackout provision limits experiments. No mechanical ventilation.
1 Poor relationship to Science staff facilities.
1 Fixed furniture layout restricts flexibility and supervision. Fume cupboards against wall limits visibility of experiments by students.
0 WIFI enabled
Second means of escape through chemical store/prep room.
Narrow door does not meet current requirements. Access by way of poor quality lift opening directly into Lab 2
Lab 4 L414 0/1 Room area below norm.
1 No blackout provision limits experiments. Mechanical vent.
1 Poor relationship to Science staff facilities.
1 Fixed furniture layout restricts flexibility and supervision. Fume cupboards against wall limits visibility of experiments by students.
0 WIFI enabled
Second means of escape through chemical store/prep room.
Access by way of poor quality lift opening directly into Lab 2
Spaces Direct Impact on Education H & S/ Security Disabled Access Comments
Type Category
feR euqinU mooR noitangiseD mooR edoC epahS/eziS tnemnorivnE noitacoL erutinruF dexiF erutcurtsarfnI TCI A B C D hgiH muideM woL seY oN
Prep 4/5 L416 0
1 Poor ventilation
0
0
0
Lab 3 and 4 second means of escape is through the prep area, potentially impeded by furniture and equipment.
Room layout makes use and access difficult.
Lab 5 L420 0/1 Room area marginal.
1 No blackout provision limits experiments. Mechanical vent.
1 Poor relationship to Science staff facilities.
1 Fixed furniture layout restricts flexibility and supervision.
0 WIFI e nabled
Second means of escape through chemical store/prep room.
Access by way of poor quality lift opening directly into Lab 2 at far end of science ‘string’ of rooms
Lab 6 L442 0/1 Room area marginal.
1 No blackout provision limits experiments. Mechanical ventilation.
1 Poor relationship to Science staff facilities.
1 Fixed furniture layout restricts flexibility and supervision. Lack of storage
0 WIFI e nabled
Second means of escape through chemical store/prep room.
Access by way of poor quality lift opening directly into Lab 2 then lengthy narrow corridor.
Spaces Direct Impact on Education H & S/ Security Disabled Access Comments
Type Category
euqinU mooR feR noitangiseD mooR edoC epahS/eziS tnemnorivnE noitacoL erutinruF dexiF erutcurtsarfnI TCI A B C D hgiH muideM woL seY oN
Prep 6/7 L443A 0
1 Poor ventilation
0
0
0
Door widths and layout make use and access difficult.
Lab 6 and 7 second means of escape for each classroom is through the prep area and adjoining classroom, potentially impeded by furniture and equipment.
Lab 7 L443 1 Room area below norm.
1 No blackout provision limits experiments. No mechanical vent.
2 Bad relationship to other science rooms due to linear layout and lack of corridor access
1 Fixed furniture layout restricts flexibility and supervision. Fume cupboards against wall limits visibility of experiments by students.
0 WIFI enabled
Second means of escape through chemical store/prep room and adjacent classroom.
Access by way of poor quality lift opening directly into Lab 2 and then along narrow corridor and through adjacent classroom and prep areas.
Staff L445 0
0
2 Bad relationship to other science rooms due to linear layout and lack of corridor access
0
0 WIFI enabled
But access is through adjacent classrooms and prep room.
Spaces Direct Impact on Education H & S/ Security Disabled Access Comments
Type Category
euqinU mooR feR noitangiseD mooR edoC epahS/eziS tnemnorivnE noitacoL erutinruF dexiF erutcurtsarfnI TCI A B C D hgiH muideM woL seY oN
Lab 8 C355 0/1 Room area marginal.
0
2 Remote from remainder of science accommodation. On ground floor 150m from nearest science room.
2 No fume cupboard.
0 WIFI enabled
Remote from remainder of department. Staffing issues.
Classroom used if there is a need for disabled access due to difficulties of using existing lift.
Spaces Direct Impact on Education H & S/ Security Disabled Access Comments
Typ Category
loohcS mooR feR tessA mooR edoC epahS/eziS tnemnorivnE noitacoL erutinruF dexiF erutcurtsarfnI TCI A B C D hgiH muideM woL seY oN
Room 8 classroom R185 2 Room severely undersized.
1 Wind noise and draughts.
0
1 Lockers in room reduces usable area.
0
Shortage of space around furniture.
Narrow doorways do not meet current requirements.
Room9 classroom R189 2 Room severely undersized.
1 Wind noise and draughts.
0
1 Lockers in room reduces usable area.
0
Shortage of space around furniture.
Narrow doorways do not meet current requirements.
Spaces Direct Impact on Education H & S/ Security Disabled Access Comments
Typ Category
loohcS mooR feR tessA mooR edoC epahS/eziS tnemnorivnE noitacoL erutinruF dexiF erutcurtsarfnI TCI A B C D hgiH muideM woL seY oN
Room 10 classroom R202 2 Room severely undersized.
1 Wind noise and draughts.
0
1 Lockers in room reduces usable area.
0
Shortage of space around furniture.
Narrow doorways do not meet current requirements.
Room 11 classroom R203 2 Room severely undersized.
1 Wind noise and draughts.
0
1 Lockers in room reduces usable area.
0
Shortage of space around furniture.
Narrow doorways do not meet current requirements.
Store R204 1 Small room
0
0
0
0
Narrow doorways do not meet current requirements.
Spaces Direct Impact on Education H & S/ Security Disabled Access Comments
Typ Category
loohcS mooR feR tessA mooR edoC epahS/eziS tnemnorivnE noitacoL erutinruF dexiF erutcurtsarfnI TCI A B C D hgiH muideM woL seY oN
Room 12 classroom R206 1 Room slightly undersized.
1 Wind noise and draughts. Audible footfall from laboratory above.
0
0
0
Store R206a 1 Small store.
0
0
0
0
Narrow doorways do not meet current requirements.
Room 13 staffroom R207 0
1 Wind noise and draughts.
0
0
0
Narrow doorway does not meet current requirements.
Spaces Direct Impact on Education H & S/ Security Disabled Access Comments
Typ Category
loohcS mooR feR tessA mooR edoC epahS/eziS tnemnorivnE noitacoL erutinruF dexiF erutcurtsarfnI TCI A B C D hgiH muideM woL seY oN
Room PS2 classroom U241 2 Room severely undersized.
0
1 Remote from remainder of maths classrooms
0
0
Shortage of space around furniture.
Narrow doorways do not meet current requirements.
Store U241a 1 Small store.
0
0
0
0
Narrow doorway does not meet current requirements.
Spaces Direct Impact on Education H & S/ Security Disabled Access Comments
Type Category
euqinU mooR feR noitangiseD mooR edoC epahS/eziS tnemnorivnE noitacoL erutinruF dexiF erutcurtsarfnI TCI A B C D hgiH muideM woL seY oN
Classrm F2 F339 Room size well below standards (BB98)
1 Poor lighting and no mechanical vent. Acoustic separation poor. Adjacent occupiers concerned about level of noise from classrooms.
1 Extremity of dead end corridor
0
1 Lack of data and power outlets
Narrow corridors and dead end location results in overcrowding of corridors during class change. Layout of rooms inhibits supervision of corridor spaces.
Narrow corridors hampers free movement. Narrow doorways do not meet current requirements.
Classrm F3 F338 1 Room size well below standards (BB98)
1 Acoustic separation poor. Adjacent occupiers concerned about level of noise from classrooms.
1 Extremity of dead end corridor
0
1 Lack of data and power outlets
Narrow corridors and dead end location results in overcrowding of corridors during class change.
Narrow co rridors hampe rs free move m ent. Narr ow doo rways do not meet current requirements.
Spaces Direct Impact on Education H & S/ Security Disabled Access Comments
Type Category
euqinU mooR feR noitangiseD mooR edoC epahS/eziS tnemnorivnE noitacoL erutinruF dexiF erutcurtsarfnI TCI A B C D hgiH muideM woL seY oN
Classrm F4 F336 1 Room size well below standards (BB98)
1 Acoustic separation poor. Adjacent occupiers concerned about level of noise from classrooms.
1 Extremity of dead end corridor
0
1 Lack of data and power outlets
Narrow corridors and dead end location results in overcrowding of corridors during class change. Layout of rooms inhibits supervision of corridor spaces. Windows open over external path.
Narrow corridors hampers free movement. Narrow doorways do not meet current requirements.
Group room F5 F341 0
1 Acoustic separation poor. Adjacent occupiers concerned about level of noise from classrooms.
1 Extremity of dead end corridor
0
1 Lack of data and power outlets
Narrow corridors and dead end location results in overcrowding of corridors during class change. Layout of rooms inhibits supervision of corridor spaces. Windows open over external path.
Narrow corridors hampers free movement.
Group room F6 F340 0
1 Acoustic separation poor. Adjacent occupiers concerned about level of noise from classrooms.
1 Extremity of dead end corridor
0
1 Lack of data and power outlets
Narrow corridors and dead end location results in overcrowding of corridors during class change. Layout of rooms inhibits supervision of corridor spaces. Windows open over external path.
Narrow corridors hampers free movement. Narrow doorways do not meet current requirements.
Spaces Direct Impact on Education H & S/ Security Disabled Access Comments
Type Category
euqinU mooR feR noitangiseD mooR edoC epahS/eziS tnemnorivnE noitacoL erutinruF dexiF erutcurtsarfnI TCI A B C D hgiH muideM woL seY oN
Office F7 F331 0 Doubles as small ‘speaking room’
0
1 Extremity of dead end corridor
0
0
Narrow corridors and dead end location results in overcrowding of corridors during class change. Layout of rooms inhibits supervision of corridor spaces.
Narrow corridors hampers free movement. Narrow doorways do not meet current requirements.
Store F8 F334 0
0
1 Extremity of dead end corridor
0
0
Narrow corridors and dead end location results in overcrowding of corridors during class change.
Narrow co rridors hampe rs free move m ent.
Staff room 0
1 Acoustic separation poor. Skylight only natural light.
1 Extremity of dead end corridor
0
0
Narrow corridors and dead end location results in overcrowding of corridors during class change. Layout of rooms inhibits supervision of corridor spaces.
Narrow corridors hampers free movement. Narrow doorways do not meet current requirements.
Spaces Direct Impact on Education H & S/ Security Disabled Access Comments
Type Category
loohcS mooR fer tessA mooR edoC epahS/eziS tnemnorivnE noitacoL erutinruF dexiF erutcurtsarfnI TCI A B C D hgiH muideM woL seY oN
Classrm H7 H320 1 Good sized room but without storage cbd/room.
0
0
0
0
Risks from corridor congestion
Narrow doors do not meet current regulations.
Office H318 1 Small staff base and office for Humanities Department. 8 staff.
0
0
0
0
Lack of privacy for individual Heads of Subject.
Narrow doors do not meet current regulations.
Classrm H8 H316 1 Room area marginal
1 Room overheats.
0
0
0
Risks from corridor congestion
Narrow doors do not meet current regulations.
Spaces Direct Impact on Education H & S/ Security Disabled Access Comments
Type Category
loohcS mooR fer tessA mooR edoC epahS/eziS tnemnorivnE noitacoL erutinruF dexiF erutcurtsarfnI TCI A B C D hgiH muideM woL seY oN
Classrm C3 C356 2 Room severely undersized.
0
1 Not adjoining C2.
0
0
Lack of space around desks.
Narrow doors do not meet current regulations. Lack of space restricts movement of wheelchairs.
Store C3 C356a 1 Store too small for needs resulting in books being stored in classroom which is already too small.
0
0
0
0
Spaces Direct Impact on Education H & S/ Security Disabled Access Comments
Type Category
euqinU mooR feR noitangiseD mooR edoC epahS/eziS tnemnorivnE noitacoL erutinruF dexiF erutcurtsarfnI TCI A B C D hgiH muideM woL seY oN
Common room U426 1 Not sufficient space for entire 6th Form of 140-150 students. Lack of spaces for individual study.
2 Extremes of temperature and very bad acoustics limit use of space.
0
0
0
Y13 common room U415 1 Insufficient space for private study for Y13
1 Poor environmental control.
0
0
0
Narrow door widths do not comply with current requirements for wheelchair access.
Spaces Direct Impact on Education H & S/ Security Disabled Access Comments
Type Category
euqinU mooR feR noitangiseD mooR edoC epahS/eziS tnemnorivnE noitacoL erutinruF dexiF erutcurtsarfnI TCI A B C D hgiH muideM woL seY oN
Study room U427 0
1 Wide seasonal temperature variations and poor acoustics.
0
0
0
Computer area 1 Too small to meet demand for computer facilities.
1 Temp variations and poor acoustics.
0
0
0
Emotional First aid U429 0
1 No natural daylight.
0
0
0
Narrow door widths do not comply with current requirements for wheelchair access.
Spaces Direct Impact on Education H & S/ Security Disabled Access Comments
Type Category
euqinU mooR feR noitangiseD mooR edoC epahS/eziS tnemnorivnE noitacoL erutinruF dexiF erutcurtsarfnI TCI A B C D hgiH muideM woL seY oN
Group room U422 0
0
0
0
0
Narrow door widths do not comply with current requirements for wheelchair access.
Head’s office U424 0
0
0
0
0
Door width too narrow.
Teaching room U430 1 Classroom too small for year group.
0
0
0
0
Narrow door widths do not comply with current requirements for wheelchair access.
Spaces Direct Impact on Education H & S/ Security Disabled Access Comments
Type Category
loohcS mooR fer tessA mooR edoC epahS/eziS tnemnorivnE noitacoL erutinruF dexiF erutcurtsarfnI TCI A B C D hgiH muideM woL seY oN
Classrm H1 H311 1 Room of insufficient area for class size. Working area per student is insufficient.
1 Lack of suitable temperature and ventilation. Room hot and stuffy throughout the year.
1 Location on narrow corridor which serves classrooms on both sides creates issues re class change.
1 Centrally located fixed furniture can obscure view of teacher and white board.
0
Door width does not meet current requirements re wheelchair access.
Classrm H2 H313 1 Room of insufficient area for class size. Far corner of room too far from teaching area/whiteboards.
1 Lack of suitable temperature and ventilation. Room hot and stuffy throughout the year.
1 Location on narrow corridor which serves classrooms on both sides creates issues re class change.
1 Centrally located fixed furniture can obscure view of teacher and white board.
0
Door width does not meet current requirements re wheelchair access.
Spaces Direct Impact on Education H & S/ Security Disabled Access Comments
Type Category
loohcS mooR fer tessA mooR edoC epahS/eziS tnemnorivnE noitacoL erutinruF dexiF erutcurtsarfnI TCI A B C D hgiH muideM woL seY oN
Office H315 0
0
0
0
0
Door width does not meet current requirements re wheelchair access.
Small group room H315a 0
1 Constant noise from IT cabinet renders the room unsuitable for sound recording and a poor space for teaching. Lack of adequate ventilation.
1 Access through office or Classroom H2
0
1 Noise from IT cabinet.
Door width does not meet current requirements re wheelchair access.
Spaces Direct Impact on Education H & S/ Security Disabled Access Comments
Type Category
euqinU mooR feR noitangiseD mooR edoC epahS/eziS tnemnorivnE noitacoL erutinruF dexiF erutcurtsarfnI TCI A B C D hgiH muideM woL seY oN
Studio D211 1 Small studio
0
0
0
0
Narrow doors do not meet current requirements for wheelchair access.
Store D211a 1 Small store
0
0
0
0
Narrow doors do not meet current requirements for wheelchair access.
Spaces Direct Impact on Education H & S/ Security Disabled Access Comments
Type Category
euqinU mooR feR noitangiseD mooR edoC epahS/eziS tnemnorivnE noitacoL erutinruF dexiF erutcurtsarfnI TCI A B C D hgiH muideM woL seY oN
Studio D212 1 Shape of space creates difficulties in teaching and supervision of students.
0
0
0
0
Store D212a 1
0
0
0
0
Narrow door does not meet current requirements for wheelchair access.
Anti room D212b 0
0
0
0
0
Narrow door does not meet current requirements for wheelchair access.
Spaces Direct Impact on Education H & S/ Security Disabled Access Comments
Type Category
euqinU mooR feR noitangiseD mooR edoC epahS/eziS tnemnorivnE noitacoL erutinruF dexiF erutcurtsarfnI TCI A B C D hgiH muideM woL seY oN
Dark room D212c 0 Not currently used as a dark room.
0
0
0
0
Studio D213 1 D1113 and D1114 are combined to form KS4 studio.
0
0
0
0
Kiln room D213a 0 Not currently used.
0
0
0
0
Spaces Direct Impact on Education H & S/ Security Disabled Access Comments
Type Category
euqinU mooR feR noitangiseD mooR edoC epahS/eziS tnemnorivnE noitacoL erutinruF dexiF erutcurtsarfnI TCI A B C D hgiH muideM woL seY oN
Store D213b 1 Small store.
0
0
0
0
Narrow door does not meet current requirements for wheelchair access.
Store D213c 1
0
0
0
0
Narrow door does not meet current requirements for wheelchair access.
Studio D214 1 D1113 and D1114 are combined to form KS4 studio.
0
0
0
0
Spaces Direct Impact on Education H & S/ Security Disabled Access Comments
Type Category
euqinU mooR feR noitangiseD mooR edoC epahS/eziS tnemnorivnE noitacoL erutinruF dexiF erutcurtsarfnI TCI A B C D hgiH muideM woL seY oN
Store D214a 1 Small store
0
0
0
0
Narrow door does not meet current requirements for wheelchair access.
6th form studio D215 1 Small studio restricts number of students and size of work pieces.
0
0
0
0
Store D215a 1
0
0
0
0
Narrow door does not meet current requirements for wheelchair access.
Spaces Direct Impact on Education H & S/ Security Disabled Access Comments
Type Category
euqinU mooR feR noitangiseD mooR edoC epahS/eziS tnemnorivnE noitacoL erutinruF dexiF erutcurtsarfnI TCI A B C D hgiH muideM woL seY oN
Store D214b 0
0
0
0
0
Narrow door does not meet current requirements for wheelchair access.
Spaces Direct Impact on Education H & S/ Security Disabled Access Comments
Type Category
euqinU mooR feR noitangiseD mooR edoC epahS/eziS tnemnorivnE noitacoL erutinruF dexiF erutcurtsarfnI TCI A B C D hgiH muideM woL seY oN
Teaching area D217 0
1 Large expanse of basic glazing leads to wide variations in temperature.
0
0
0
This room leads onto other labs and is therefore a bit of a corridor.
Wkshop and staff base D218 0
1 Only natural light is from a skylight.
0
0
0
No facility for undertaking prep work producing fumes or dust – has to be carried out in classrooms.
Spaces Direct Impact on Education H & S/ Security Disabled Access Comments
Type Category
euqinU mooR feR noitangiseD mooR edoC epahS/eziS tnemnorivnE noitacoL erutinruF dexiF erutcurtsarfnI TCI A B C D hgiH muideM woL seY oN
Head’s office D219 0
1
0
0
0
Narrow door does not meet current requirements for wheelchair access.
Wkshop/ main store D218a 1 Shape/size of workshop preludes the correct setting out of major timber cutting equipment.
1 Noisy when in use. Dust extract system for DT dept in corner of room.
0
1 Fixed items hamper distribution of stores.
0
Lack of suitable work area markings around machinery. Poor floor finish.
Store D220 0
0
0
0
0
Narrow door does not meet current requirements for wheelchair access.
Spaces Direct Impact on Education H & S/ Security Disabled Access Comments
Type Category
euqinU mooR feR noitangiseD mooR edoC epahS/eziS tnemnorivnE noitacoL erutinruF dexiF erutcurtsarfnI TCI A B C D hgiH muideM woL seY oN
Graphics classrm DT6 D223 1 Small classroom – tight for groups of 22+ students.
1
0
1 Plotter and 3D printers reduce usable space in room.
0
Congestion in small room creates hazard.
Heat treatmt room D222 2 Room too small to allow adequate supervision or teaching. Restricts number of students able to use.
2 Size of room exacerbates issues with fume extract and heat buildup.
0
1 Items of equipment take up large proportion of floor space.
0
Tight space and hazardous processes increase health and safety risks.
Wheelchair maneuverability severely restricted by size of room and fixed equipment.
Lab DT7 D225 1 Small classroom – tight for groups of 22+ students doing practicals.
1 No mechanical ventilation other than dust extract from machines.
0
0
0
Tight space for practical work.
Spaces Direct Impact on Education H & S/ Security Disabled Access Comments
Type Category
euqinU mooR feR noitangiseD mooR edoC epahS/eziS tnemnorivnE noitacoL erutinruF dexiF erutcurtsarfnI TCI A B C D hgiH muideM woL seY oN
Lab DT 8 D224 2 Very small laboratory, use restricted to A level students due to size limitations.
1 No mechanical vent, room warm in summer term.
0
0
0
Constricted space with consequential trip hazards.
Food room DT1 D245 1 Lab too small for class sizes. No prep room
1 Lab very warm, windows do not open far enough to help with ventilation. Condensation renders floors slippy. Noisy window fans.
0
1 Insufficient space in lab for fridges etc. no provision for cooling food.
1 No IT provision in room.
Environmental conditions and lack of space generates a high H&S risk. No hand wash facility.
Narrow door does not meet current requirements for wheelchair access.
Lab DT2 D243 1 Small general teaching laboratory.
0
0
0
0
Narrow door does not meet current requirements for wheelchair access.
Spaces Direct Impact on Education H & S/ Security Disabled Access Comments
Type Category
euqinU mooR feR noitangiseD mooR edoC epahS/eziS tnemnorivnE noitacoL erutinruF dexiF erutcurtsarfnI TCI A B C D hgiH muideM woL seY oN
Store D244 1 Store too small, adjacent corridor used for storage.
0
1 Storage of foodstuffs should be in classroom.
0
0
Risk of contamination during movement of foodstuffs.
Narrow door does not meet current requirements for wheelchair access.
Store D244a 1 Store too small, adjacent corridor used for storage.
0
1 Storage of foodstuffs should be in classroom.
0
0
Risk of contamination during movement of foodstuffs.
Narrow door does not meet current requirements for wheelchair access.
Lab Textiles DT3 D236 1 Redundant food preparation area limits functionality.
1 Room generally cold.
0
1 Insufficient space for sewing machines.
0
Narrow door does not meet current requirements for wheelchair access.
Spaces Direct Impact on Education H & S/ Security Disabled Access Comments
Type Category
euqinU mooR feR noitangiseD mooR edoC epahS/eziS tnemnorivnE noitacoL erutinruF dexiF erutcurtsarfnI TCI A B C D hgiH muideM woL seY oN
Store D236a 1 Small store, not large enough for rolls of material or large work pieces.
0
0
0
0
Narrow door does not meet current requirements for wheelchair access.
Store D252 1 Large store but aspect ratio renders much of the space useless.
1 No control of condition for storage of materials or work pieces.
0
0
0
Narrow door does not meet current requirements for wheelchair access.
Textiles Classrm DT4 D254 1 Room of insufficient size for KS3 classes of 22+ students. No dedicated space for A Level students.
1 Cold room with no specific ventilation.
1 Remote from Art Dept for A Level Art Design Textiles students and shared technician.
1 Washing facilitates for dying and cleaning of work pieces is insufficient.
0
Narrow door does not meet current requirements for wheelchair access.
Spaces Direct Impact on Education H & S/ Security Disabled Access Comments
Type Category
loohcS mooR feR tessA mooR edoC epahS/eziS tnemnorivnE noitacoL erutinruF dexiF erutcurtsarfnI TCI A B C D hgiH muideM woL seY oN
Studio 1 H310 2 Good sized space seriously compromised by two columns near the centre of the room
1 Hard acoustic and lack of soundproofing
0
0
1 Poor provision of data and power outlets
Lack of storage space.
Narrow door width does not comply with current requirements for wheelchair access.
Studio 2 H314 1 Small space well below recommended area (BB98)
1 Hard acoustic and lack of soundproofing
0
0
1 Poor provision of data and power outlets
Lack of storage space. Narrow adjacent corridors.
Narrow door width does not comply with current requirements for wheelchair access.
Spaces Direct Impact on Education H & S/ Security Disabled Access Comments
Type Category
euqinU mooR feR noitangiseD mooR edoC epahS/eziS tnemnorivnE noitacoL erutinruF dexiF erutcurtsarfnI TCI A B C D hgiH muideM woL seY oN
Classrm 1 M170 0
1 Hard acoustic and lack of soundproofing
0
0
0
Lack of storage space for instruments leading to storage in corridors. Narrow corridors.
Narrow doors to accommodation from narrow corridors and ramped access corridor.
Classrm 2 M172 0
1 Hard acoustic and lack of soundproofing
0
0
0
Lack of storage space for instruments leading to storage in corridors. Narrow corridors.
Narrow doors to accommodation from narrow corridors and ramped access corridor.
Spaces Direct Impact on Education H & S/ Security Disabled Access Comments
Type Category
euqinU mooR feR noitangiseD mooR edoC epahS/eziS tnemnorivnE noitacoL erutinruF dexiF erutcurtsarfnI TCI A B C D hgiH muideM woL seY oN
Practice 1 M166 1 Small room with limited capacity for group practice.
1 Poor acoustic isolation
0
0
1 Poor provision of data and power outlets
Lack of storage space for instruments leading to storage in corridors. Narrow corridors.
Narrow doors to accommodation from narrow corridors
Practice 2 M168 1
1
0
0
1
Lack of storage space for instruments leading to storage in corridors. Narrow corridors.
Narrow doors to accommodation from narrow corridors and ramped corridor.
IT room M170a 1 Small internal room too small for large group work
1 No natural light or ventilation
0
0
0
Narrow doors to accommodation from narrow corridors and ramped corridor.
Spaces Direct Impact on Education H & S/ Security Disabled Access Comments
Typ Category
euqinU mooR feR noitangiseD mooR edoC epahS/eziS tnemnorivnE noitacoL erutinruF dexiF erutcurtsarfnI TCI A B C D hgiH muideM woL seY oN
Library P137 0
1 Stuffy and warm in summer, air movement supplemented by floor mounted fans. Acoustics generally good but can be affected by footfall from 6th Form area above.
0
0
0
Supervision by single member of staff.
Library office P192 0
1 Very warm all year.
0
0
0
Narrow doors do not meet current requirements.
Spaces Direct Impact on Education H & S/ Security Disabled Access Comments
Typ Category
loohcS mooR feR tessA mooR edoC epahS/eziS tnemnorivnE noitacoL erutinruF dexiF erutcurtsarfnI TCI A B C D hgiH muideM woL seY oN
Study room R190 1 Small room for quiet study. Capacity 6.
1 Mechanically ventilated but gets warm when used.
0
0
0
Narrow doors do not meet current regulations.
Computer room 1 Small ‘bookable’ IT classroom with capacity of 17, remainder of class use computers in the library.
1 Mechanically ventilated but gets warm when used.
0
0
0
Supervision of room and library overflow not satisfactory.
Spaces Direct Impact on Education H & S/ Security Disabled Access Comments
Type Category
euqinU mooR feR noitangiseD mooR edoC epahS/eziS tnemnorivnE noitacoL erutinruF dexiF erutcurtsarfnI TCI A B C D hgiH muideM woL seY oN
Sports hall S367 0
1 Hard acoustic reduces comprehension during teaching.
1 Remote location causes loss of teaching time.
0
1 Lack of audio or video resource
External access over trafficked area in front of school
Some threshold issues.
Sports hall storage S367a 1 Storage space inadequate
0
0
0
0
External access over trafficked area in front of school
Spaces Direct Impact on Education H & S/ Security Disabled Access Comments
Type Category
euqinU mooR feR noitangiseD mooR edoC epahS/eziS tnemnorivnE noitacoL erutinruF dexiF erutcurtsarfnI TCI A B C D hgiH muideM woL seY oN
Gym G383 2 Aspect ratio and size preclude use for court sports. Used as exam room.
1
1 Remote location causes loss of teaching time.
0
1 Lack of audio or video resource
External access over trafficked area in front of school.
Some threshold issues.
Gym storage G383a 1 Storage space inadequate, large items stored in gym reducing usable space.
0
0
0
0
Items stored in gym.
Changing Rooms G384 1 Only one male and one female.
G390 2 Very poor environmental conditions.
1 Remote from external playing fields.
1 Poor layout of benches, no lockers for lettings or student use.
0
Spaces Direct Impact on Education H & S/ Security Disabled Access Comments
Type Category
euqinU mooR feR noitangiseD mooR edoC epahS/eziS tnemnorivnE noitacoL erutinruF dexiF erutcurtsarfnI TCI A B C D hgiH muideM woL seY oN
PE Classrm G381 0 Size suitable but there is only one classroom. Use of another classroom in school reduces teaching time.
1 Poor lighting and general ventilation conditions. Used for public lettings.
1 Remote location can cause loss of teaching time.
0
1 Lack of data and power points.
External access over trafficked area in front of school.
Threshold issues.
Staff office 0
0
1 Remote from remainder of school but centrally located in PE Dept.
0
1 Lack of data and power points.
External access over trafficked area in front of school.
Threshold issues.
Fitness suite S471 1 Small cramped space.
2 Poor environmental conditions.
2 First floor with no disabled access
1 Equipment cramped in space.
1 Lack of data and power points.
Equipment tightly arranged, intrusive roof structure.
First floor, no lift provision.
Spaces Direct Impact on Education H & S/ Security Disabled Access Comments
Type Category
euqinU mooR feR noitangiseD mooR edoC epahS/eziS tnemnorivnE noitacoL erutinruF dexiF erutcurtsarfnI TCI A B C D hgiH muideM woL seY oN
Head’s office G382 1 Small room
1 No external windows, poor ventilation.
0
0
0
Narrow door does not comply with current requirements for wheelchair access.
General storage 1 Lack of appropriate storage,
0
2 Items and furniture stored in corridors.
0
0
Corridors used for storage creates hazard.
Narrow door does not comply with current requirements for wheelchair access.
External fields 0
0
0
0
0
Spaces Direct Impact on Education H & S/ Security Disabled Access Comments
Type Category
loohcS mooR fer tessA mooR edoC epahS/eziS tnemnorivnE noitacoL erutinruF dexiF erutcurtsarfnI TCI A B C D hgiH muideM woL seY oN
SENCO office F332 0
0
1 Fragmented disposition of accommodation results in management and staffing difficulties.
0
0
Access door is narrower than required by current requirements..
SC 1 H324 2 Cognitive area – lack of area severely restricts usage by vulnerable students particularly at lunchtime. There are 227 students who are recognized as potential users of the accommodation.
0
0
0
1 Lack of data and power outlets
Access door is narrower than required by current legislation. External thresholds do not meet current regulations.
Spaces Direct Impact on Education H & S/ Security Disabled Access Comments
Type Category
loohcS mooR fer tessA mooR edoC epahS/eziS tnemnorivnE noitacoL erutinruF dexiF erutcurtsarfnI TCI A B C D hgiH muideM woL seY oN
SC 2 H324a 2 Nurture area – use restricted by current size of room.
0
0
0
1 Lack of data and power outlets.
Access door is narrower than required by current requirements for wheelchair access.
Kitchen 0
0
0
0
0
SC 3 unit H319 1/2 Adequacy of space varies from year to year depending on specific needs of students.
0
0
0
1 Lack of data and power outlets.
Access door is narrower than required by current requirements. External thresholds do not meet current regulations.
Spaces Direct Impact on Education H & S/ Security Disabled Access Comments
Type Category
loohcS mooR fer tessA mooR edoC epahS/eziS tnemnorivnE noitacoL erutinruF dexiF erutcurtsarfnI TCI A B C D hgiH muideM woL seY oN
Unit Physio/ shower H321 0
0
0
0
0
Access door is narrower than required by current requirements for wheelchair access.
Unit physio/ wc H327 0
0
0
0
0
Access door is narrower than required by current requirements for wheelchair access.
Unit Sensory room H317 1 Small space off of corridor.
1 Curtained off space.
2 Located off of corridor – lack of privacy
0
0
Spaces Direct Impact on Education H & S/ Security Disabled Access Comments
Type Category
loohcS mooR fer tessA mooR edoC epahS/eziS tnemnorivnE noitacoL erutinruF dexiF erutcurtsarfnI TCI A B C D hgiH muideM woL seY oN
Unit Group room H325 0
0
0
0
0
Access door is narrower than required by current requirements for wheelchair access.
Unit office H300 1 Small room unsuited to current use
0
0
0
0
Access door is narrower than required by current requirements for wheelchair access.
Unit ‘prefab’ 5 7 0
0
2 Remote from remainder of unit and consequently difficult to manage and underused.
0
1 Lack of data and power outlets
Access door is narrower than required by current requirements. External thresholds do not meet current regulations. Access by ramp.
Spaces Direct Impact on Education H & S/ Security Disabled Access Comments
Type Category
loohcS mooR fer tessA mooR edoC epahS/eziS tnemnorivnE noitacoL erutinruF dexiF erutcurtsarfnI TCI A B C D hgiH muideM woL seY oN
SC 4 Mobile 5 4 0
0
2 Remote from remainder of unit and consequently difficult to manage. Two staff required at all times.
0
1 Lack of data and power outlets.
Access door is narrower than required by current requirements. External thresholds do not meet
Spaces Direct Impact on Education H & S/ Security Disabled Access Comments
Type Category
euqinU mooR feR noitangiseD mooR edoC epahS/eziS tnemnorivnE noitacoL erutinruF dexiF erutcurtsarfnI TCI A B C D hgiH muideM woL seY oN
Staff corridor A125 0
0
0
0
0
Congestion related risks
Only wheelchair accessible from outside. Steps on corridor to admin area.
English corridor R153 1 Narrow corridor with high usage resulting in congestion.
0
0
0
0
Congestion related risks.
English corridor R159 1 Narrow corridor with high usage resulting in congestion.
1 Toilet hand driers create acoustic problems.
0
0
0
Congestion related risks
Spaces Direct Impact on Education H & S/ Security Disabled Access Comments
Type Category
euqinU mooR feR noitangiseD mooR edoC epahS/eziS tnemnorivnE noitacoL erutinruF dexiF erutcurtsarfnI TCI A B C D hgiH muideM woL seY oN
English corridor R165 1 Narrow corridor junction with stair from upper floor.
0
0
0
0
Congestion related risks
Maths corridor R1 7 1 Narrow corridor with high usage resulting in congestion.
1 Toilet hand driers create acoustic problems.
0
0
0
Congestion related risks
Maths corridor R210 1 Narrow corridor junction with stair from upper floor.
0
0
0
0
Congestion related risks
Spaces Direct Impact on Education H & S/ Security Disabled Access Comments
Type Category
euqinU mooR feR noitangiseD mooR edoC epahS/eziS tnemnorivnE noitacoL erutinruF dexiF erutcurtsarfnI TCI A B C D hgiH muideM woL seY oN
Art Corridor D210 1 Narrow dead end corridor.
0
0
0
0
Congestion related risks
No wheelchair access other than through classrooms.
D&T corridor 1 Narrow corridor.
0
0
0
0
D&T corridor D250 1 Narrow corridor.
0
0
0
0
Spaces Direct Impact on Education H & S/ Security Disabled Access Comments
Type Category
euqinU mooR feR noitangiseD mooR edoC epahS/eziS tnemnorivnE noitacoL erutinruF dexiF erutcurtsarfnI TCI A B C D hgiH muideM woL seY oN
Access to D&T/Art D235 1 Narrow corridor at junction of main thoroughfare.
0
0
0
0
Congestion related risks.
Wheelchair access to D&T and Art by way of platform lift.
Cooking corridor D242 1 Narrow corridor.
0
0
1 Storage cupboards and filing cabinets along walls.
0
Congestion related risks.
Library corridor P135 1 Wide corridor with severe bottlenecks at each end. Sometimes used as a chair/table store.
0
0
0
0
Congestion related risks.
Spaces Direct Impact on Education H & S/ Security Disabled Access Comments
Type Category
euqinU mooR feR noitangiseD mooR edoC epahS/eziS tnemnorivnE noitacoL erutinruF dexiF erutcurtsarfnI TCI A B C D hgiH muideM woL seY oN
Music corridor M149 1 Very narrow, partially sloping dead end corridor.
1 Poor acoustics.
0
0
0
Congestion related risks.
Music corridor M14 1 Very narrow dead end corridor
1 Poor acoustics.
0
0
0
Congestion related risks.
Human’ corridor H326 1 Narrow partially sloping corridor
1 Poor acoustics.
0
1 Filing cabinets and other storage along walls.
0
Congestion related risks. Classrooms both sides of narrow corridor.
Spaces Direct Impact on Education H & S/ Security Disabled Access Comments
Type Category
euqinU mooR feR noitangiseD mooR edoC epahS/eziS tnemnorivnE noitacoL erutinruF dexiF erutcurtsarfnI TCI A B C D hgiH muideM woL seY oN
Human’ corridor H351 1 Narrow corridor.
1 P oor acoustics
0
0
0
Congestion related risks.
Language corridor F330 1 Narrow partially sloping corridor.
1 Poor acoustics.
1 Dead end corridor.
0
0
Congestion related risks.
Human’ corridor C351 1 Corridor constricted at each end.
1 Poor acoustics.
0
0
0
Congestion related risks.
Spaces Direct Impact on Education H & S/ Security Disabled Access Comments
Type Category
euqinU mooR feR noitangiseD mooR edoC epahS/eziS tnemnorivnE noitacoL erutinruF dexiF erutcurtsarfnI TCI A B C D hgiH muideM woL seY oN
PE corridor C365 1 Narrow corridor.
1 Poor acoustics.
0
0
0
Congestion related risks.
Staff corridor First floor A46 0
0
0
0
0
No lift to first floor in this area.
Science corridor L400 1 Narrow corridor.
0
0
0
0
Congestion related risks
Spaces Direct Impact on Education H & S/ Security Disabled Access Comments
Type Category
euqinU mooR feR noitangiseD mooR edoC epahS/eziS tnemnorivnE noitacoL erutinruF dexiF erutcurtsarfnI TCI A B C D hgiH muideM woL seY oN
Science/ 6th form corridor L409 1 Narrow, partially sloping corridor
2 Extremes of temperature and very poor aesthetics – roof ductwork, ponding etc.
0
0
0
Congestion related risks.
By way of small lift which opens out into Lab 2.
Science/ 6th form corridor L411 1 Narrow corridor
2 Extremes of temperature and very poor aesthetics – roof ductwork, ponding etc.
0
0
0
Congestion related risks.
By way of small lift which opens out into Lab 2.
Science/ 6th form corridor L418 1 Narrow corridor
0
0
0
0
Congestion related risks.
By way of small lift which opens out into Lab 2.
Spaces Direct Impact on Education H & S/ Security Disabled Access Comments
Type Category
euqinU mooR feR noitangiseD mooR edoC epahS/eziS tnemnorivnE noitacoL erutinruF dexiF erutcurtsarfnI TCI A B C D hgiH muideM woL seY oN
Stairwell R208 1 Narrow stair.
0
0
0
0
Congestion related risks.
No lift access to first floor in this area.
Spaces Direct Impact on Education H & S/ Security Disabled Access Comments
Type Category
loohcS mooR fer tessA mooR edoC epahS/eziS tnemnorivnE noitacoL erutinruF dexiF erutcurtsarfnI TCI A B C D hgiH muideM woL seY oN
Dining room K130 2 Dining hall vastly undersized. Main hall has to be used to cater for the numbers of diners.
0
1 Proximity to main entrance causes congestion at break and lunch times.
0
0
Lack of space between tables and around server area creates potential hazard.
Frozen goods store K132 1 Large freezer in rear of store. Inefficient use of space.
1 Condensation/moisture from freezer affecting ceiling finish in store room.
2 Frozen goods store accessed from dining area and stocked by way of main school entrance.
1 Freezer takes up much of the available space with the door swing further limiting storage.
0
Potential hazard moving goods into and out of store.
Narrow door does not meet current requirements for wheelchair access.
Spaces Direct Impact on Education H & S/ Security Disabled Access Comments
Type Category
loohcS mooR fer tessA mooR edoC epahS/eziS tnemnorivnE noitacoL erutinruF dexiF erutcurtsarfnI TCI A B C D hgiH muideM woL seY oN
Kitchen K134 2 Kitchen area very constrained limiting opportunities.
1 Acoustics poor.
0
2 Congested area.
0
Congested kitchen area - risk of injury.
No space for maneuvering of wheelchairs. Kitchen not set up for wheelchair use.
Servery K134 2 Server area severely congested at lunch times.
1 Acoustics poor.
0
1 Till layout determined by available space. Queuing requires supervision.
0
Congested area – risk of injury.
Wheelchair accessible but constrained space.
Spaces Direct Impact on Education H & S/ Security Disabled Access Comments
Type Category
loohcS mooR fer tessA mooR edoC epahS/eziS tnemnorivnE noitacoL erutinruF dexiF erutcurtsarfnI TCI A B C D hgiH muideM woL seY oN
Office R155 1 Small office for site manager and assistant.
1 No natural light
0
0
1 Lack of data and power outlets
Narrow door does not comply with current requirements re wheelchair access.
Zone
1 – Entrance area Lack of visual ‘presence’ and gravitas.
2 – Admin area A mix of single and two storey flat and pitched roof structures, vaguely ‘Art Deco’ in style. Centrally located offices and service accommodation.
3 – Kitchen/dining/hall Centrally located facility but location close to main entrance causes congestion at break and lunch times. Combined area of hall and dining area just sufficient to deal with in excess of 700 meals at lunch time. No adequate storage space for tables and chairs when not in use.
4 – English, maths and science Two storey brick structure with pitched slated roof. Maths and English classrooms generally below acceptable area for class sizes. Science classrooms on first floor generally closer to minimum area required for class sizes. Corridors feeding these rooms well below acceptable width.
5 – Humanities Humanities subjects relatively closely grouped but without sufficient classrooms for all teachers. Geography classrooms generously sized and linked by a folding partition.
6 – Languages Single storey masonry construction under a tiled pitched roof. Dead end location.
7 – PE Remotely located facility housed in a mix of old military accommodation and newer sports hall. Changing and gymnasium facilities are well below standard.
8 – D&T/Art Main portion of department housed within Vic Hallam Derwent System modular timber framed single storey building which allows a significant level of flexibility in layout but which suffers from a lack of environmental control and age related decay. The structure was built in the late 1950’s with an expected life span of xx years. Wheelchair access by way of small platform lift adjacent to interface with Hall. Remainder of department housed in single storey flat roofed structure.
9 – Library/6th form ‘Lightweight’ interjection into former open quad. Completed in 2000? Very poor environmental conditions and acoustics due to inappropriate roof covering.
10 – Music and Drama Music and Drama facilities lacking in rehearsal and performance space. Location remote from Art negatively impacts on cooperation between the creative arts.
11 - SEN Slightly fragmented facility across two main building areas and two external ‘mobile classrooms’ caused issues with supervision and control. No dedicated external activity area.
GH Ex Central Z Greenhouse Area
GH Ex Central Z Item Element Material Finish Condition Priority Cost Comment Maintenance Item Future Attention Required
GH Ex Central Z Pedestrian Area Greenhouse Aluminium C 1 Greenhouse frame is aged guttering to the base has end covers missing and broken downpipe, there is one broken glass pain with tape holing it together. Any ferrous fixings are very likely to be corroded. The rendering to the base walls has delaminated to the opening and in other local areas
GH Ex Central Z Pedestrian Area Drainage Gullies Steel A 3 Gullies are worn corroded but serviceable
GH Ex Central Z Pedestrian Area Pathways Concrete C 2 Concrete paths have cracked in almost all areas, the joints are not displaced and are serviceable generally; there is one large recently installed area which is in a good condition
GH Ex Central Z Pedestrian Area Pathways Macadam C 2 Macadam sections have settled and become uneven in some areas, sections are poor but generally serviceable
GH Ex Central Z Limited Access Area Pathways Slabs B 3 The slabs are aged and generally serviceable (Slabbed area is used for storage and only partly visible for inspection)
GH Ex Central Z Pedestrian Area Walling Brick B 3 Walling adjacent to the Sports Hall door is aged but generally serviceable
GH Ex Central Z Pedestrian Area Planters Brick C 3 Planter to the side on the Greenhouse has a section where the brickwork has broken, approximately 20 bricks are missing; there is no capping to the top of this walling
GH Ex Central Z Limited Access Area Fencing Timber Not known E 1 Fencing around the storage area has broken posts and panels
GH Ex Central Z Pedestrian Area Shed/Out‐building Timber Not known A 3
GH Ex Central Z Pedestrian Area Railings Steel Painted B 2 Railings to ramps are aged and have corrosion to the fixings
CR Ex Central Z Circulation Roundabout
CR Ex Central Z Item Element Material Finish Condition Priority Cost Comment Maintenance Item Future Attention Required
CR Ex Central Z Vehicle Area Roadway Surface Macadam A 3 Settlement has caused some local undulations to the surface which is evident against some of the Kerbs. The surface is generally is good condition
CR Ex Central Z Vehicle Area Road Kerbs Concrete B 3 Aged in all areas with some local fractures, generally sound; the upstand of the Kerbs is not consistent due presumably to the settlement. The design function of the Kerbs upstand to repel car wheels has been compromised particularly around the island
CR Ex Central Z Vehicle Area White Lines Painted B 2 Lines are worn in places Yes
CR Ex Central Z Vehicle Area Drainage Gullies Steel A 3 Aged but in a satisfactory condition
CR Ex Central Z Vehicle Area Drainage Covers Steel A 3 Aged but in a satisfactory condition
CR Ex Central Z Pedestrian Area Pathways Macadam A 3 Aged but in a satisfactory condition
CR Ex Central Z Pedestrian Area Pathways Slabs B 2 Paving to the central recreation area have broken and jointing has started to breakdown in several areas Yes
CR Ex Central Z Pedestrian Area Back Edge Kerbs Concrete A 3 Aged but in a satisfactory condition
CR Ex Central Z Pedestrian Area Street Furniture Timber Not known D 1 Tables and seating are rotting in places, edge features to the sides of pathways have deteriorated and are falling apart Yes
CR Ex Central Z Pedestrian Area Walling Natural Stone A 3 Satisfactory condition
Cp/F Ex Central Z Carpark School Frontage
Cp/F Ex Central Z Item Element Material Finish Condition Priority Cost Comment Maintenance Item Future Attention Required
Cp/F Ex Central Z Vehicle Area Roadway Surface Macadam A 3 Settlement has caused some local undulations to the surface which is evident against some of the Kerbs. The surface is generally is good condition
Cp/F Ex Central Z Vehicle Area Road Kerbs Concrete B 3 Aged in all areas with some local fractures, generally sound; the upstand of the Kerbs is not consistent due presumably to the settlement
Cp/F Ex Central Z Vehicle Area White Lines Painted B 2 Lines are worn in places
Cp/F Ex Central Z Vehicle Area Parking Bay Surface Macadam A 3 Settlement has caused some local undulations to the surface which is evident against some of the Kerbs. The surface is generally is good condition, there is detritus and evidence of standing water areas
Cp/F Ex Central Z Vehicle Area Drainage Gullies Steel A 3 Aged but in a satisfactory condition
Cp/F Ex Central Z Vehicle Area Drainage Covers Steel A 3 Aged but in a satisfactory condition
Cp/F Ex Central Z Pedestrian Area Pathways Macadam C 2 Sections adjacent to Blocks J & K are uneven in places, settlement has occurred to a small degree and the surface is uneven in places. Path adjacent to the Tennis Court has sections missing which pose as trip hazards
Cp/F Ex Central Z Pedestrian Area Pathways Slabs A 2 A few local fractures / cracks but generally satisfactory
Cp/F Ex Central Z Pedestrian Area Pathways Concrete E 1 Concrete surface adjacent to the Kitchen has large cracks and substantial gaps which could cause a trip hazard
Cp/F Ex Central Z Limited Access Area Street Furniture Timber Painted A 2 Flag Pole is very aged and has corrosion to metal parts
Cp/F Ex Central Z Limited Access Area Hardstand Gravel (Loose) Painted B 2 The ground cover is this area is uneven, with poor inset wooden treads
Cp/F Ex Central Z Pedestrian Area Railings Steel Powder Coating A 3 Colouring has faded significantly but the functionally is in satisfactory condition
Cp/F Ex Central Z Pedestrian Area Bollards Steel Painted A 3 Satisfactory condition
Cp/F Ex Central Z Pedestrian Area Bollards Timber Treated A 3 Satisfactory condition
Cp/F Ex Central Z Pedestrian Area Seating Steel Powder Coating A 2 Fixing down bolts are corroding
Cp/F Ex Central Z Pedestrian Area Walling Rendered Painted A 3 Satisfactory condition
Cp/F Ex Central Z Pedestrian Area Walling Rendered D 2 The north boundary wall has hairline cracks and delaminating render local to the construction joints. The wall is starting to lean forward out of the vertical slightly
Cp/F Ex Central Z Pedestrian Area Walling Rendered D 1 The small retaining wall adjacent to the Triple Tennis Courts has cracking and several sections where the concrete capping has broken off and or been displaced. Broken materials are laying in the local grass
Cp/F Ex Central Z Pedestrian Area Steps Brick A 3 Satisfactory condition
Cp/F Ex Central Z Pedestrian Area Walling Rendered A 3 Satisfactory condition (Bin Store)
Cp/D Ex West Z Carpark Block D
Cp/D Ex West Z Item Element Material Finish Condition Priority Cost Comment Maintenance Item Future Attention Required
Cp/D Ex West Z Vehicle Area Roadway Surface Concrete E 2 The ramp access has an uneven surface with sections of old brick walling substructure forming the surface locally
Cp/D Ex West Z Vehicle Area Road Kerbs Concrete E 2 There is kerbing completely failed to the short Kerbs section of the ramp
Cp/D Ex West Z Vehicle Area Roadway Surface Consolidated Stone E 2 The consolidated stone has become pitted from continued vehicle turning, several pot‐holes and depressions are >100mm
Cp/D Ex West Z Vehicle Area Parking Bay Surface Consolidated Stone E 2 The consolidated stone has become pitted from continued vehicle turning, several pot‐holes and depressions are >100mm
Cp/D Ex West Z Vehicle Area Back Edge Kerbs Timber E 2 Timber strip edge between the stone surface and grass areas has become overgrown and has worn where visible
Cp/D Ex West Z Vehicle Area Walling Rendered D 2 The north boundary wall has hairline cracks and delaminating render local to the construction joints. The wall is starting to lean forward out of the vertical slightly
Cp/D Ex West Z Vehicle Area Drainage Covers Steel C 2 Inspection chamber cover is not suitably rated for vehicle passage, security screws are missing and the cover seating ring has not been encapsulated in concrete
TTC Ex Central Z Triple Tennis Court
TTC Ex Central Z Item Element Material Finish Condition Priority Cost Comment Maintenance Item Future Attention Required
TTC Ex Central Z Sports Area Hardstand Macadam A 3 Surface has some settlement local to the perimeter Kerbs and undulation but remains satisfactory
TTC Ex Central Z Sports Area White Lines Painted A 3 Satisfactory condition
TTC Ex Central Z Sports Area Drainage Gullies Steel B 3 The gully grate is set approximately 100mm below the local surface level
TTC Ex Central Z Sports Area Back Edge Kerbs Concrete A 3 Satisfactory condition
TTC Ex Central Z Sports Area Fencing Steel Galvanised C 2 Fencing support wires have broken at most posts, connection rings are corroding. There are gaps in the wiring on the gate
Cp/H Ex North Z Carpark Horseshoe & Lane
Cp/H Ex North Z Item Element Material Finish Condition Priority Cost Comment Maintenance Item Future Attention Required
Cp/H Ex North Z Vehicle Area Roadway Surface Macadam B 2 There is one section of the road surface which has started to break‐up Yes
Cp/H Ex North Z Vehicle Area Road Kerbs Concrete A 3 Satisfactory condition
Cp/H Ex North Z Vehicle Area White Lines Painted B 2 Paint has worn and may be indistinguishable is poor light and or wet conditions
Cp/H Ex North Z Vehicle Area Parking Bay Surface Macadam A 3 Satisfactory condition
Cp/H Ex North Z Vehicle Area Drainage Gullies Steel A 3 Satisfactory condition
Cp/H Ex North Z Vehicle Area Drainage Gullies Concrete B 3 There is one channel section to the roadside which has displaced and brakes the continuity of the channel Yes
Cp/H Ex North Z Vehicle Area Drainage Covers Steel A 3 Satisfactory condition
Cp/H Ex North Z Pedestrian Area Pathways Macadam B 2 There is a section of the pathway where the macadam appears to have been lain Thin, the material is beginning to break up. Some local settlement has occurred local to the sign posts
Cp/H Ex North Z Pedestrian Area Back Edge Kerbs Concrete A 3 Satisfactory condition
Cp/H Ex North Z Pedestrian Area Railings Steel Powder Coating A 3 Satisfactory condition
Cp/H Ex North Z Pedestrian Area Planters Brick B 3 Pointing has started to deteriorate local to the top capping header course
Cp/H Ex North Z Pedestrian Area Walling Natural Stone B 2 Small local sections of the stone walling along the north boundary have started to break‐up Yes
Cp/H Ex North Z Pedestrian Area Walling Brick D 2 Capping to the small retaining wall has been dislodged along sections of one wall
Cp/H Ex North Z Pedestrian Area Walling Brick C 2 Small section of pointing has started to deteriorate
Cp/H Ex North Z Vehicle Area Street Furniture Steel Painted B 2 Overhead light column has corrosion on the neck of the column
MR Ex Central Z Main Entrance Road
MR Ex Central Z Item Element Material Finish Condition Priority Cost Comment Maintenance Item Future Attention Required
MR Ex Central Z Vehicle Area Roadway Surface Macadam B 3 Macadam has started to break‐up along the junction with the Main Road
MR Ex Central Z Vehicle Area Road Kerbs Concrete A 3 some chips/crack to Kerbs but generally satisfactory condition
MR Ex Central Z Vehicle Area White Lines Painted B 2 Paint has worn and may be indistinguishable is poor light and or wet conditions
MR Ex Central Z Vehicle Area Drainage Gullies Steel A 3 Satisfactory condition
MR Ex Central Z Vehicle Area Drainage Covers Steel A 3 Satisfactory condition
MR Ex Central Z Pedestrian Area Pathways Macadam A 3 Satisfactory condition
MR Ex Central Z Pedestrian Area Walling Natural Stone A 3 Satisfactory condition
HP Ex Central Z Hockey Pitch (Single)
HP Ex Central Z Item Element Material Finish Condition Priority Cost Comment Maintenance Item Future Attention Required
HP Ex Central Z Sports Area Hardstand Macadam A 3 Surface has some settlement local to the perimeter Kerbs and undulation but remains satisfactory. There is some detritus and evidence of standing water
HP Ex Central Z Sports Area White Lines Painted A 3 Satisfactory condition
HP Ex Central Z Sports Area Drainage Gullies Steel A 3 Satisfactory condition
HP Ex Central Z Sports Area Drainage Covers Steel A 3 Satisfactory condition
HP Ex Central Z Sports Area Back Edge Kerbs Concrete A 3 Satisfactory condition
HP Ex Central Z Sports Area Fencing Steel Galvanised C 2 Fencing support wires have broken at most posts, connection rings are corroding. There are gaps in the wiring on the gate and there are two posts that have moved away from the vertical
BGR Ex North Z Block G Road
BGR Ex North Z Item Element Material Finish Condition Priority Cost Comment Maintenance Item Future Attention Required
BGR Ex North Z Vehicle Area Roadway Surface Macadam B 3 There is some tearing local to one chamber cover but generally satisfactory
BGR Ex North Z Vehicle Area Parking Bay Surface Macadam A 3 Satisfactory condition
BGR Ex North Z Vehicle Area Road Kerbs Concrete A 3 Satisfactory condition
BGR Ex North Z Vehicle Area White Lines Painted A 3 Satisfactory condition
BGR Ex North Z Vehicle Area Drainage Gullies Steel A 3 Satisfactory condition
BGR Ex North Z Vehicle Area Drainage Covers Steel A 3 Satisfactory condition
BGR Ex North Z Vehicle Area Walling Natural Stone A 3 Satisfactory condition
EAR Ex East Z East Access Road
EAR Ex East Z Item Element Material Finish Condition Priority Cost Comment Maintenance Item Future Attention Required
EAR Ex East Z Vehicle Area Roadway Surface Macadam C 1 Macadam has broken up is several local sections
EAR Ex East Z Vehicle Area Hardstand Concrete C 2 Cracking is widespread
EAR Ex East Z Vehicle Area Drainage Covers Steel B 2 One chamber has sunk and the cover has deflected
EAR Ex East Z Vehicle Area Drainage Gullies Steel A 3 Satisfactory condition
EAR Ex East Z Vehicle Area Walling Natural Stone D 2 The cement/concrete capping to the entire boundary wall has been displaced all the way along. One section adjacent to the MUA Substation has started to collapse
EAR Ex East Z Vehicle Area Walling Brick A 3 Old but generally functional
GC Ex East Z Groundman's Compound
GC Ex East Z Item Element Material Finish Condition Priority Cost Comment Maintenance Item Future Attention Required
GC Ex East Z Vehicle Area Roadway Surface Macadam B 3
GC Ex East Z Vehicle Area Hardstand Concrete C 2 Cracking is widespread
GC Ex East Z Vehicle Area Drainage Covers Steel A 3 Old but satisfactory
GC Ex East Z Vehicle Area Walling Brick A 3 Old but generally functional. One brick missing from the top corner of one wall
GC Ex East Z Vehicle Area Walling Natural Stone C 2 The cement/concrete capping to the entire boundary wall has been displaced
GC Ex East Z Vehicle Area Gates Steel Galvanised A 3 Adjustment required but generally functional Yes
Cp/C Ex East Z Carpark Block C
Cp/C Ex East Z Item Element Material Finish Condition Priority Cost Comment Maintenance Item Future Attention Required
Cp/C Ex East Z Vehicle Area Roadway Surface Consolidated Stone E 2 The consolidated stone has become pitted from continued vehicle turning, several pot‐holes and depressions are >100mm
Cp/C Ex East Z Vehicle Area Road Kerbs Concrete B 3 Aged in all areas with some local fractures, generally sound
Cp/C Ex East Z Vehicle Area Parking Bay Surface Consolidated Stone E 2 The consolidated stone has become pitted from continued vehicle turning, several pot‐holes and depressions are >100mm
Cp/C Ex East Z Vehicle Area Drainage Covers Steel B 2 One cover cannot be lifted, but generally functional
Cp/C Ex East Z Vehicle Area Gates Steel Galvanised A 3 Adjustment required but generally functional Yes
Cp/C Ex East Z Vehicle Area Walling Natural Stone C 2 The cement/concrete capping to the entire boundary wall has been displaced
IC/N Ex North Z Internal Courtyard (between A‐5 & E‐6)
IC/N Ex North Z Item Element Material Finish Condition Priority Cost Comment Maintenance Item Future Attention Required
IC/N Ex North Z Limited Access Area Hardstand Slabs B 2 Worn and uneven surface
IC/N Ex North Z Limited Access Area Drainage Gullies Steel A 2 Worn but functional
IC/N Ex North Z Limited Access Area Drainage Covers Steel A 2 Worn but functional
IC/N Ex North Z Limited Access Area Walling Rendered A 3 Worn but functional
IC/S Ex South Z Internal Courtyard (between B‐1 & E‐1)
IC/S Ex South Z Item Element Material Finish Condition Priority Cost Comment Maintenance Item Future Attention Required
IC/S Ex South Z Pedestrian Area Hardstand Slabs B 2 Worn but functional
IC/S Ex South Z Pedestrian Area Drainage Gullies Steel B 2 Worn but functional
IC/S Ex South Z Pedestrian Area Drainage Covers Steel B 2 Worn but functional
IC/S Ex South Z Pedestrian Area Back Edge Kerbs Concrete B 2 Worn but functional
IC/S Ex South Z Pedestrian Area Street Furniture Timber A 3
IC/W Ex West Z Internal Courtyard (between J‐3 & D‐1)
IC/W Ex West Z Item Element Material Finish Condition Priority Cost Comment Maintenance Item Future Attention Required
IC/W Ex West Z Pedestrian Area Hardstand Timber Treated A 3
IC/W Ex West Z Pedestrian Area Pathways Timber Treated A 3
IC/W Ex West Z Limited Access Area Pathways Gravel (Loose) A 3
IC/W Ex West Z Pedestrian Area Fencing Timber Treated A 3
IC/W Ex West Z Pedestrian Area Street Furniture Timber Treated A 3
IC/W Ex West Z Pedestrian Area Drainage Covers Steel B 2 Worn but functional
AWP Ex South Z All weather Sports Pitch
AWP Ex South Z Item Element Material Finish Condition Priority Cost Comment Maintenance Item Future Attention Required
AWP Ex South Z Pedestrian Area Pathways Macadam A 3 Some weeds are present but the surface is generally sound
AWP Ex South Z Pedestrian Area Back Edge Kerbs Concrete A 3 Satisfactory condition
AWP Ex South Z Pedestrian Area Fencing Steel Galvanised A 3 There is widespread deposits to the powder coated fencing which appears to be salts, local areas where individual wires are bent. Two panels have been removed, presumably for access. There is some local patches where the paint has delaminated from Galvanised posts. Posts along the North elevation appear to have been re‐set into the ground. Generally in sound condition
AWP Ex South Z Pedestrian Area Street Furniture Steel Galvanised A 3 Sports Lighting Columns ‐ There is light surface corrosion staining in some locations, the columns are in sound condition generally
AWP Ex South Z Pedestrian Area Steps Slabs B 2 There is one broken slab at the top of three steps out of the East side gate
AWP Ex South Z Pedestrian Area Hardstand Astro‐turf A 3 Surface is aged but generally sound, there is some local moss growth
GAS Ex West Z Gas Building
GAS Ex West Z Item Element Material Finish Condition Priority Cost Comment Maintenance Item Future Attention Required
GAS Ex West Z Wall Cover Rendered B 3 Aggregate loss in places
GAS Ex West Z Wall Doorways Rendered A 3
GAS Ex West Z Wall Doors Timber A 3
GAS Ex West Z Wall RWP Downpipes UPVC B 1 Broken downpipe connections
GAS Ex West Z Wall Fixings Proprietary A 2 Lights
GAS Ex West Z Wall Penetrations Brick A 3 Multiple airbricks
GAS Ex West Z Roof Cover Mineral Felt A 3
GAS Ex West Z Roof Eaves/Fascia UPVC A 3
GAS Ex West Z Roof RWP Guttering UPVC A 3
OIL Ex Central Z Oil Storage Building
OIL Ex Central Z Item Element Material Finish Condition Priority Cost Comment Maintenance Item Future Attention Required
OIL Ex Central Z Wall Cover Dash B 2 Several cracks and patchy loss of chippings but generally serviceable
OIL Ex Central Z Wall Doorways Rendered B 2 Not fully sealed around the frame
OIL Ex Central Z Wall Doors Timber C 2 Rotting door
OIL Ex Central Z Wall RWP Downpipes UPVC A 2 Aged but serviceable
OIL Ex Central Z Wall Parapets Dash B 2 Several cracks and patchy loss of chippings but generally serviceable
OIL Ex Central Z Wall Fixings Services A 3 Light fitting
OIL Ex Central Z Wall Steps Metal B 2 Corroding metalwork
OIL Ex Central Z Roof Cover Corrigated Board A 3 Possibly asbestos boards
OIL Ex Central Z Roof Cover Concrete A 3
OIL Ex Central Z Roof Eaves/Fascia Concrete A 3
OIL Ex Central Z Roof Eaves/Fascia Timber B 2 Delaminating paint, and wood is deteriorating
OIL Ex Central Z Roof Soffit Concrete A 3
OIL Ex Central Z Roof RWP Guttering UPVC A 2 Aged but serviceable, vegetation is present
OIL Ex Central Z Roof Flashing Lead A 3
OIL Ex Central Z Roof Side Abutment Lead A 3
BKR Ex South Z Block K Road / Track
BKR Ex South Z Item Element Material Finish Condition Priority Cost Comment Maintenance Item Future Attention Required
BKR Ex South Z Vehicle Area Roadway Surface Consolidated Stone E 2 The consolidated stone has become pitted from continued vehicle use, extensively pot‐holed and depressions are >150mm
BKR Ex South Z Vehicle Area Road Kerbs Concrete B 3 Kerbs to one side of the rack only are old, work but serviceable
BKR Ex South Z Vehicle Area Parking Bay Surface Consolidated Stone E 2 The consolidated stone has become pitted from continued vehicle turning, several pot‐holes and depressions are >100mm
BKR Ex South Z Vehicle Area Parking Bay Surface Concrete A 3 Generally sat
BKR Ex South Z Vehicle Area Drainage Gullies Steel B 2 Worn but functional
BKR Ex South Z Vehicle Area Drainage Covers Steel C 2 Local erosion to the consolidated stone is resulting in one cover effectively above the ground level
BKR Ex South Z Vehicle Area Hardstand Concrete A 3
Electrical Installation Condition Report Requirements for Electrical Installations - BS 7671:2018 (IET Wiring Regulations 18th Edition)
Information for recipients:
The purpose of this report is to confirm, so far as reasonably practicable, whether or not the electrical installation is in a satisfactory condition for continued service (see Section E). The report should identify any damage, deterioration, defects and/or conditions which may give rise to danger (see Section K). The person ordering the report should have received the original report and the inspector should have retained a duplicate. The original Report should be retained in a safe place and be made available to any person inspecting or undertaking work on the electrical installation in the future. If the property is vacated, this report will provide the new owner / occupier with details of the condition of the electrical installation at the time the report was issued. Where the installation incorporates residual current devices (RCDs) there should be a notice at or near the devices stating that they should be tested every 6 months. For safety reasons it is important that these instructions are followed. Section D (Extent and Limitations) should identify fully the extent of the installation covered by this report and any limitations on the inspection and testing. The Inspector should have agreed these aspects with the person ordering the report and with other interested parties (licencing authority, insurance company, mortgage provider and the like() before the inspection was carried out. Some operational limitations such as inability to gain access to parts of the installation or an item of equipment may have been encountered during the inspection. The inspector should have noted these in Section D. For items classified in Section K as C1 (“Danger Present”), the safety of those using the installation is at risk, and it is recommended that a skilled person or persons competent in electrical installation work undertakes the necessary remedial work immediately. For items classified in Section K as C2 (“Potentially Dangerous”), the safety of those using the installation may be at risk and it is recommended that a skilled person or persons competent in electrical installation work undertakes the necessary remedial work as a matter of urgency. Where it has been stated in Section K that an observation requires further investigation code FI the inspection has revealed an apparent deficiency which may result on a code C1 or C2 could not, due to the extent or limitations of this inspection, be fully identified. Such observations should be investigated as soon as possible. A further examination of the installation will be necessary, to determine the nature and extent of the apparent deficiency (see Section F). For safety reasons, the electrical installation should be re-inspected at appropriate intervals by a skilled person or persons competent in such work. The recommended date by which the next inspection is due is stated in Section F of the report under ‘Recommendations’ and on label at or near to the consumer unit/distribution board.
2 7 4 8 6 0 0 0 0 1 2 1 9
Page 2 of 7
A Details of the Installation
Client Public Estates and Housing Division Installation
Address Department of Infrastructure Hills Meadow Peel Road Douglas Isle of Man Address Castle Rushen High School Mobile One Arbory Road Castletown
Postcode IM1 5EB Postcode IM9 1RE
B Reason for producing this report This form is to be used only for reporting on the condition of an existing installation.
Periodic Inspection and Test of Electrical Installation
Date(s) on which the inspection and testing were carried out 26 /10/2020 to 26/10/2020
C Details of installation which is the subject of this report
Description of premises Domestic Commercial
Estimated age of the wiring system 18 years
Evidence of alterations or addition Yes No Not apparent if 'Yes', estimated 5 years
Records of installation available Yes No Records held by NA
Date of last inspection Not Known Electrical Installation Certificate No. or previous Inspection Report No. N/A
D Extent of electrical installation covered by this report: Agreed Limitations and Operational Limitations (Regulations 653.2)
100% of circuits None
Operational limitations including the reasons see page no 1 Agreed with: NA
The inspection and testing detailed within this report and accompanying schedule has been carried out in accordance with BS 7671: 2018 amended to 2019
It should be noted that cables concealed within trunkings and conduits, under floors, in roof spaces and generally within the fabric of the building or underground have not been inspected unless specifically agreed between the client and inspector prior to the inspection. An inspection should be made within an accessible roof space housing other electrical equipment.
E
General conditions of the installation (in terms of safety)
Suitable for continued use.
Overall assessment of the installation in terms of its suitability for continued use SATISFACTORY *UNSATISFACTORY
F Recommendations
Where the overall assessment of the suitability of the installation for continued use above is stated as UNSATISFACTORY I/we recommend that any observations classified as ‘Danger present’ (code C1) or ‘Potential dangerous’ (code C2) are acted upon as a matter of urgency. Investigation without delay is recommended for observations identified as ‘Further Investigation required’ (code FI). Observations classified as ‘Improvement recommended’ (code C3) should be given due
consideration. Subject to the necessary remedial action being taken, I/we recommend that the installation is further inspected and tested by 26/10/2025 (date)
G Declaration
I/we being the person(s) responsible for the inspection and the testing of the electrical installation (as indicated by my/our signatures below), particulars of which are described above, having exercised reasonable skill and care when carrying out the inspection and testing hereby declare that the information in this report, including the observations and the attached schedules, provides an accurate assessment of the condition of the electrical installation taking into account the stated extent and limitations in section D of this report.
Company Name: Signature: Position: Date: Inspected and tested by Authorised for issue by
Membership No. Name:
Address Signature:
Position:
Postcode Date:
H Schedule(s)
1 schedule(s) of inspection and 1 schedule(s) of test results are attached.
The attached schedule(s) are part of this document and this report is valid only when they are attached to it.
2 7 4 8 6 0 0 0 0 1 2 1 9
Page 3 of 7
I Supply characteristics and earthing arrangements
Earthing Arrangements
Number & Type of live conductors
TN-S
AC DC
TT
No. of phases 3
Please specify
No. of wires 4
Nature of Supply Parameters (Note: (1) by enquiry, (2) by enquiry or by measurement)
Nominal voltage, U/U0 (1) 400/230 v Nominal frequency, f(1) 50 H
Prospective fault current, Ipf (2) 1.77 kA 0.26 Ω Or Zdb Source of Circuit
Supply Protective Device BS (EN) 60898 Type 2 Rated Current 63 A
Other Sources of Supply (as detailed on attached schedule)
J Particulars of installation referred to in this report
Details of installation Earth Electrode (where applicable) Type (e.g. rod(s), tape etc ) N/A
Location N/A Electrode resistance to ear th N/A Ω Distributors facility Installation Earth Electrode
Main Protective Conductors Material csa ( ü) or Value Maximum Demand (load) N/A Amps KVA
Earthing Conductor Copper 16 Ω (connection / continuity) ( ü)or Value (ü) or Value
Protective Bonding Conductor (to extraneous-conductive-parts) Copper Water installation Ω To structural steel Ω
Gas installation pipes Ω To lightning protection Ω
Main Supply Conductor Copper Oil installation pipes Ω Othe r Ω
Main Switch Location
Fuse/device rating or setting 100 A Voltage rating 400 V
If RCD main switch: Rated residual operating current I Δn 300 mA
23227 N o. of Poles 4
Rated time delay 300 m
Current Rating 100 A
Measured operating trip time 289 ms
Observations
Referring to the attached schedule of inspection and test results, and subject to the limitations at Section D.
No remedial work required
Danger present. Risk of Injury. Immediate remedial action required.
Potentially dangerous. Urgent remedial action required.
Improvement recommended.
Further Investigation required without delay
Item No. Observations Code
1 DB1 Circuit 5L3 Office Heater - there is no voltage reading at the heater. The relay was tested and this is satisfactory. Further investigation is recommended.
One of the above codes, as appropriate, has been allocated to each of the observations made above and/or any attached observation sheets to indicate to the person(s) responsible for the installation the degree of urgency for remedial action. Danger present. Risk of Injury. Immediate remedial action required. Potentially dangerous. Urgent remedial action required. Improvement recommended. Further Investigation required without delay 1
Danger present. Risk of Injury. Immediate remedial action required.
Potentially dangerous. Urgent remedial action required.
Improvement recommended.
Further Investigation required without delay 1
2 7 4 8 6 0 0 0 0 1 2 1 9
Page 4 of 7
Outcomes
Acceptable condition: Unacceptable condition: State Improvement recommended: Further Investigation: Not Verified: Limitation: Not Applicable:
or
In the outcome column use the codes above. Provide additional comment where appropriate. C1/C2/C3 and FI coded items to be recorded in section K of the condition report.
Item No. Description Outcome
1.0 External Condition Of Intake Equipment (Visual Inspection Only) Where inadequacies are encountered, it is recommended that the person ordering the report informs the appropriate authority 1.1 Service cable 1.2 Service head 1.3 Earthing arrangement 1.4 Meter tails 1.5 Metering equipment 1.6 Isolator (where present) 2.0 Presence Of Adequate Arrangements For Other Sources Such As Microgenerators (551.6; 551.7) 3.0 Earthing / Bonding Arrangements (411.3; Chap 54) 3.1 Presence and condition of distributor’s earthing arrangement (542.1.2.1; 542.1.2.2) 3.2 Presence and condition of earth electrode connection where applicable (542.1.2.3) 3.3 Provision of earthing/bonding labels at all appropriate locations (514.13.1) 3.4 Confirmation of earthing conductor size (542.3; 543.1.1) 3.5 Accessibility and condition of earthing conductor at MET arrangement (543.3.2) 3.6 Confirmation of main protective bonding conductor sizes (544.1) 3.7 Condition and accessibility of main protective bonding conductor/connections (543.3.2; 544.1.2) 3.8 Accessibility and condition of other protective bonding connections (543.3.1; 543.3.2) 4.0 Consumer Unit(s) / Distribution Board(s) 4.1 Adequacy of working space/accessibility to consumer unit/distribution board (132.12; 513.1) 4.2 Security of fixing (134.1.1) 4.3 Condition of enclosure(s) in terms of IP rating etc (416.2) 4.4 Condition of enclosure(s) in terms of fire rating etc (421.1.201; 526.5) 4.5 Enclosure not damaged/deteriorated so as to impair safety (651.2) 4.6 Presence of main linked switch (as required by 462.1.201) 4.7 Operation of main switches (functional check) (643.10) 4.8 Manual operation of circuit-breakers and RCD(s) to prove disconnection (643.10) 4.9 Correct identification of circuit details and protective devices (514.8.1; 514.9.1) 4.10 Presence of RCD six-monthly test notice at or near consumer unit/distribution board (514.12.2) 4.11 Presence of non-standard (mixed) cable colour warning notice at or near consumer unit/distribution board (514.14) 4.12 Presence of alternative supply warning notice at or near consumer unit/distribution board (514.15) 4.13 Presence of other required labelling (please specify) (Section 514) Compatibility of protective devices, bases and other components; correct type and rating (No signs of unacceptable thermal 4.14 damage, arcing or overheating) (411.3.2; 411.4; 411.5; 411.6; section 432.433) 4.15 Single-pole switching or protective devices in line conductor only (132.14.1; 530.3.3) Protection against mechanical damage where cables enter consumer unit/distribution board (132.14.1; 522.8.1; 522.8.5; 4.16 522.8.11) 4.17 Protection against electromagnetic effects where cables enter consumer unit/distribution board/enclosures (521.5.1) 4.18 RCD(s) provided for fault protection - includes RCBOs (411.4.204; 411.5.2; 531.2) 4.19 RCD(s) provided for additional protection / requirements - includes RCBOs (411.3.3; 415.1) 4.20 Confirmation of indication that SPD is functional (651.4) Confirmation that ALL conductor connections, including connections to busbars, are correctly located in terminals and are 4.21 tight and secure (526.1) 4.22 Adequate arrangements where a generating set operates as a switched alternative to the public supply (551.6) 4.23 Adequate arrangements where a generating set operates in parallel with the public supply (551.7) 5.0 Final Circuits 5.1 Identification of conductors (514.3.1) 5.2 Cables correctly supported throughout their run (521.10.202; 522.8.5) 5.3 Condition of insulation of live parts (416.1) 5.4 Non-sheathed cables protected by enclosure in conduit, ducting or trunking. Integrity of containment (521.10.1) 5.4.1 To include the integrity of conduit and trunking systems (metallic and plastic) 5.5 Adequacy of cables for current-carrying capacity with regard for the type and nature of installation (Section 523) 5.6 Coordination between conductors and overload protective devices (433.1; 533.2.1) 5.7 Adequacy of protective devices: type and rated current for fault protection (411.3) 5.8 Presence and adequacy of circuit protective conductors (433.3.1; Section 543) 5.9 Wiring system(s) appropriate for the type and nature of the installation and external influences (Section 522)
1.0 External Condition Of Intake Equipment (Visual Inspection Only) Where inadequacies are encountered, it is recommended that the person ordering the report informs the appropriate authority
1.1 Service cable
1.2 Service head
1.3 Earthing arrangement
1.4 Meter tails
1.5 Metering equipment
1.6 Isolator (where present)
2.0 Presence Of Adequate Arrangements For Other Sources Such As Microgenerators (551.6; 551.7)
3.0 Earthing / Bonding Arrangements (411.3; Chap 54)
3.1 Presence and condition of distributor’s earthing arrangement (542.1.2.1; 542.1.2.2)
3.2 Presence and condition of earth electrode connection where applicable (542.1.2.3)
3.3 Provision of earthing/bonding labels at all appropriate locations (514.13.1)
3.4 Confirmation of earthing conductor size (542.3; 543.1.1)
3.5 Accessibility and condition of earthing conductor at MET arrangement (543.3.2)
3.6 Confirmation of main protective bonding conductor sizes (544.1)
3.7 Condition and accessibility of main protective bonding conductor/connections (543.3.2; 544.1.2)
3.8 Accessibility and condition of other protective bonding connections (543.3.1; 543.3.2)
4.0 Consumer Unit(s) / Distribution Board(s)
4.1 Adequacy of working space/accessibility to consumer unit/distribution board (132.12; 513.1)
4.2 Security of fixing (134.1.1)
4.3 Condition of enclosure(s) in terms of IP rating etc (416.2)
4.4 Condition of enclosure(s) in terms of fire rating etc (421.1.201; 526.5)
4.5 Enclosure not damaged/deteriorated so as to impair safety (651.2)
4.6 Presence of main linked switch (as required by 462.1.201)
4.7 Operation of main switches (functional check) (643.10)
4.8 Manual operation of circuit-breakers and RCD(s) to prove disconnection (643.10)
4.9 Correct identification of circuit details and protective devices (514.8.1; 514.9.1)
4.10 Presence of RCD six-monthly test notice at or near consumer unit/distribution board (514.12.2)
4.11 Presence of non-standard (mixed) cable colour warning notice at or near consumer unit/distribution board (514.14)
4.12 Presence of alternative supply warning notice at or near consumer unit/distribution board (514.15)
4.13 Presence of other required labelling (please specify) (Section 514)
4.14 Compatibility of protective devices, bases and other components; correct type and rating (No signs of unacceptable thermal damage, arcing or overheating) (411.3.2; 411.4; 411.5; 411.6; section 432.433)
4.15 Single-pole switching or protective devices in line conductor only (132.14.1; 530.3.3)
4.16 Protection against mechanical damage where cables enter consumer unit/distribution board (132.14.1; 522.8.1; 522.8.5; 522.8.11)
4.17 Protection against electromagnetic effects where cables enter consumer unit/distribution board/enclosures (521.5.1)
4.18 RCD(s) provided for fault protection - includes RCBOs (411.4.204; 411.5.2; 531.2)
4.19 RCD(s) provided for additional protection / requirements - includes RCBOs (411.3.3; 415.1)
4.20 Confirmation of indication that SPD is functional (651.4)
4.21 Confirmation that ALL conductor connections, including connections to busbars, are correctly located in terminals and are tight and secure (526.1)
4.22 Adequate arrangements where a generating set operates as a switched alternative to the public supply (551.6)
4.23 Adequate arrangements where a generating set operates in parallel with the public supply (551.7)
5.0 Final Circuits
5.1 Identification of conductors (514.3.1)
5.2 Cables correctly supported throughout their run (521.10.202; 522.8.5)
5.3 Condition of insulation of live parts (416.1)
5.4 Non-sheathed cables protected by enclosure in conduit, ducting or trunking. Integrity of containment (521.10.1)
5.4.1 To include the integrity of conduit and trunking systems (metallic and plastic)
5.5 Adequacy of cables for current-carrying capacity with regard for the type and nature of installation (Section 523)
5.6 Coordination between conductors and overload protective devices (433.1; 533.2.1)
5.7 Adequacy of protective devices: type and rated current for fault protection (411.3)
5.8 Presence and adequacy of circuit protective conductors (433.3.1; Section 543)
5.9 Wiring system(s) appropriate for the type and nature of the installation and external influences (Section 522)
reated by NAPIT Desktop © Copyright 2020 Page 4 of 7 th Floor, Mill 3, Pleasley Vale Business Park, Mansfield, Nottinghamshire NG19 8RL NA/EICR/001
Electrical Installation Condition Report Inspection Schedule for Domestic and Similar Premises up to 100 A NA/ 2 7 4 8 6 0 0 0 0 1 2 1 9 Requirements for Electrical Installations - BS 7671:2018 (IET Wiring Regulations 18th Edition) All items inspections to confirm as EICR Page 5 of 7 appropriate, compliance with the relevant clauses in BS 7671:2018 5.10 Concealed cables installed in prescribed zones (see Section D. Extent and limitations) (522.6.202) Cables concealed under floors, above ceilings or in walls/partitions, adequately protected against damage (see Section D. 5.11 Extent and limitations) (522.6.204) 5.12 Provision of additional requirements for protection by RCD not exceeding 30 mA 5.12.1 for all socket-outlets of rating 32 A or less, unless an exception is permitted (411.3.3) 5.12.2 For the supply of mobile equipment not exceeding 32 A rating for use outdoors (411.3.3) 5.12.3 for cables concealed in walls at a depth of less than 50 mm (522.6.202; 522.6.203) 5.12.4 for cables concealed in walls/partitions containing metal parts regardless of depth (522.6.203) 5.12.5 for circuits supplying luminaires within domestic (household) premises (411.3.4) 5.13 Provision of fire barriers, sealing arrangements and protection against thermal effects (Section 527) 5.14 Band II cables segregated/separated from Band I cables (528.1) 5.15 Cables segregated/separated from communications cabling (528.2) 5.16 Cables segregated/separated from non-electrical services (528.3) 5.17 Termination of cables at enclosures - indicate extent of sampling in Section D of the report (Section 526) 5.17.1 Connections soundly made and under no undue strain (526.6) 5.17.2 No basic insulation of a conductor visible outside enclosure (526.8) 5.17.3 Connections of live conductors adequately enclosed (526.5) 5.17.4 Adequately connected at point of entry to enclosure (glands, bushes etc.) (522.8.5) 5.18 Condition of accessories including socket-outlets, switches and joint boxes (651.2(v)) 5.19 Suitability of accessories for external influences (512.2) 5.20 Adequacy of working space/accessibility to equipment (132.12; 513.1) 5.21 Single-pole switching or protective devices in line conductors only (132.14.1, 530.3.3) 6.0 Location(s) Containing A Bath Or Shower 6.1 Additional protection for all low voltage (LV) circuits by RCD not exceeding 30 mA (701.411.3.3) 6.2 Where used as a protective measure, requirements for SELV or PELV met (701.414.4.5) 6.3 Shaver sockets comply with BS EN 61558-2-5 formerly BS 3535 (701.512.3) 6.4 Presence of supplementary bonding conductors, unless not required by BS 7671:2018 (701.415.2) 6.5 Low voltage (e.g. 230 volt) socket-outlets sited at least 3 m from zone 1 (701.512.3) 6.6 Suitability of equipment for external influences for installed location in terms of IP rating (701.512.2) 6.7 Suitability of accessories and controlgear etc. for a particular zone (701.512.3) 6.8 Suitability of current-using equipment for particular position within the location (701.55) 7.0 Other Part 7 Special Installations Or Locations 7.01 List all other special installation or locations, if any (record seperately the results of particular inspections applied).
5.10 Concealed cables installed in prescribed zones (see Section D. Extent and limitations) (522.6.202)
5.11 Cables concealed under floors, above ceilings or in walls/partitions, adequately protected against damage (see Section D. Extent and limitations) (522.6.204)
5.12 Provision of additional requirements for protection by RCD not exceeding 30 mA
5.12.1 for all socket-outlets of rating 32 A or less, unless an exception is permitted (411.3.3)
5.12.2 For the supply of mobile equipment not exceeding 32 A rating for use outdoors (411.3.3)
5.12.3 for cables concealed in walls at a depth of less than 50 mm (522.6.202; 522.6.203)
5.12.4 for cables concealed in walls/partitions containing metal parts regardless of depth (522.6.203)
5.12.5 for circuits supplying luminaires within domestic (household) premises (411.3.4)
5.13 Provision of fire barriers, sealing arrangements and protection against thermal effects (Section 527)
5.14 Band II cables segregated/separated from Band I cables (528.1)
5.15 Cables segregated/separated from communications cabling (528.2)
5.16 Cables segregated/separated from non-electrical services (528.3)
5.17 Termination of cables at enclosures - indicate extent of sampling in Section D of the report (Section 526)
5.17.1 Connections soundly made and under no undue strain (526.6)
5.17.2 No basic insulation of a conductor visible outside enclosure (526.8)
5.17.3 Connections of live conductors adequately enclosed (526.5)
5.17.4 Adequately connected at point of entry to enclosure (glands, bushes etc.) (522.8.5)
5.18 Condition of accessories including socket-outlets, switches and joint boxes (651.2(v))
5.19 Suitability of accessories for external influences (512.2)
5.20 Adequacy of working space/accessibility to equipment (132.12; 513.1)
5.21 Single-pole switching or protective devices in line conductors only (132.14.1, 530.3.3)
6.0 Location(s) Containing A Bath Or Shower
6.1 Additional protection for all low voltage (LV) circuits by RCD not exceeding 30 mA (701.411.3.3)
6.2 Where used as a protective measure, requirements for SELV or PELV met (701.414.4.5)
6.3 Shaver sockets comply with BS EN 61558-2-5 formerly BS 3535 (701.512.3)
6.4 Presence of supplementary bonding conductors, unless not required by BS 7671:2018 (701.415.2)
6.5 Low voltage (e.g. 230 volt) socket-outlets sited at least 3 m from zone 1 (701.512.3)
6.6 Suitability of equipment for external influences for installed location in terms of IP rating (701.512.2)
6.7 Suitability of accessories and controlgear etc. for a particular zone (701.512.3)
6.8 Suitability of current-using equipment for particular position within the location (701.55)
7.0 Other Part 7 Special Installations Or Locations
7.01 List all other special installation or locations, if any (record seperately the results of particular inspections applied).
8.0 Schedule of Tests Results to be recorded on Schedule of Test Results
8.1 External earth loop impedance, Ze
8.2 Installation earth electrode
8.3 Prospective fault current, lpf
8.4 Continuity of Earth Conductors
8.5 Continuity of Circuit Protective Conductors
8.6 Continuity of ring final circuit
8.7 Continuity of Protective Bonding Conductors
8.8 Volt drop verified
2 7 4 8 6 0 0 0 0 1 2 1 9
Page 5 of 7
8.9 Insulation Resistance between Live Conductors
8.10 Insulation Resistance between Live Conductors & Earth
8.11 Polarity (prior to energisation)
8.12 Polarity (after energisation) including phase sequence
8.13 Earth Fault Loop Impedance
8.14 RCDs / RCBOs including selectivity
8.15 Functional testing of RCD devices
8.16 Functional testing of AFDD(s) devices
Inspector's Name:
Date: 26/10/2020
NA/ 2 7 4 8 6 0 0 0 0 1 2 1 9 EICR Page 6 of 7
Client Public Estates and Housing Division Installation Address Castle Rushen High School, Castletown Postcode IM9 1RE
Distribution board details - Complete in every case Complete only if the distribution board is not connected directly to the origin of the installation Test instrument serial number(s)
Location Storeroom Designation DB1 Supply to distribution board is from Overcurrent No. of phases Mains Intake protective device 3 Type2 BS(EN) 60898 for the distribution circuit: Nominal Voltage Rating63 400 Supply polarity confirmed Phase sequence confirmed A 2 A Z I Ti Characteristics at this distribution board ssociated RCD(if any): BS (EN) Above 30mA 3227 Operating at 1 IΔn289 ms (if appli Loop impedance Insulation resistance Continuity C10066 C10066 C10066
Num. of ways 36 d0.26 Ω No. of poles2 30mA or below cable) pf 1.77 kA Operating at 5 IΔn ms IΔn me delay (if applicable) RCDC10066
CIRCUIT DETAILS TEST RESULTS
and Circuit Line No. No. Distribution board Designation Type of wiring Ref. method No. of points Circuit conductors csa (mm²) disconnection Maximum Overcurrent protective devices capacity Breaking operating RCD BS 7671 Max. permitted Zs Other 80% Circuit impedance Ω Insulation resistance (Record lower reading) Polarity Measured Max. Zs RCD testing Manual test button operation
DB1 L / N CPC Type No. Rating (A) Ring final circuits only (measured end-to-end) check Fig 8 All circuits to be completed using R1R2 or R2, not both Test voltage L/L, L/N L/E, N/E Above 30mA IΔn 30mA or below 5 IΔn RCD AFDD
Circuit designation BS EN Number (KA) (mA) (Ω) r1 rn r2 R1 + R2 R2 V M(Ω) M(Ω) (Ω) ms ms
1L1 Heating Control A C 1 1.5 1 0.4 60898 B 2 10 300 N/A N/A N/A N/A 0.09 250 >1000 >1000 ü 0.35 289 ü N/A
1L2 Fire Alarm A C 1 1.5 1 0.4 60898 B 6 10 300 5.82 N/A N/A N/A N/A 0.36 500 >1000 >1000 ü 0.78 289 ü N/A
1L3 Spare N/A N/A N/A N/A N/A N/A N/A
2L1 Spare N/A N/A N/A N/A N/A N/A N/A
2L2 Spare N/A N/A N/A N/A N/A N/A N/A
2L3 Spare N/A N/A N/A N/A N/A N/A N/A
3L1 Spare N/A N/A N/A N/A N/A N/A N/A
3L2 Hand Dryer 8 A C 1 2.5 2.5 0.4 60898 B 10 10 300 3.49 N/A N/A N/A N/A 0.33 500 >1000 >1000 ü 0.56 289 ü N/A
3L3 Spare N/A N/A N/A N/A N/A N/A N/A
4L1 CR1 lights A C 8 1.5 1.5 0.4 60898 B 6 10 300 5.82 N/A N/A N/A N/A 0.82 250 13.2 13.2 ü 1.19 289 ü N/A
4L2 Disabled WC Downflow Heater A C 1 2.5 2.5 0.4 60898 B 10 10 300 3.49 N/A N/A N/A N/A 0.49 500 >1000 >1000 ü 0.34 289 ü N/A
4L3 Office lights A C 8 1.5 1.5 0.4 60898 B 6 10 300 5.82 N/A N/A N/A N/A 0.88 250 260 260 ü 1.23 289 ü N/A
5L1 CR1 Bay 1 Heater A C 1 2.5 2.5 0.4 60898 B 16 10 300 2.18 N/A N/A N/A N/A 0.25 500 >1000 >1000 ü 0.81 289 ü N/A
5L2 Store Water Heater A C 1 2.5 2.5 0.4 60898 B 16 10 300 2.18 N/A N/A N/A N/A 0.12 500 >1000 >1000 ü 0.49 289 ü N/A
5L3 Office Heater A C 1 2.5 2.5 0.4 60898 B 16 10 NV 2.18 N/A N/A N/A N/A NV NV NV NV N/A NV NV N/A N/A
6L1 CR1 Ring Main A C 5 2.5 2.5 0.4 61009 C 16 10 30 1.09 0.22 0.22 0.50 ü 0.17 500 198 194 ü 0.33 19.8 ü N/A
6L2 Store socket A C 3 2.5 2.5 0.4 61009 B 16 10 30 2.18 N/A N/A N/A N/A 0.93 250 43.6 43.6 ü 0.27 24.3 ü N/A
6L3 Physio Office Ring Main A C 5 2.5 2.5 0.4 61009 C 16 10 30 1.09 0.25 0.28 0.37 ü 0.61 500 >1000 >1000 ü 0.35 29.7 ü N/A
7L1 Door Access A C 1 1.5 1.5 0.4 60898 B 10 10 300 3.49 N/A N/A N/A N/A 0.18 250 >1000 >1000 ü 0.27 289 ü N/A
Details of circuits and/or installed equipment vulnerable to damage when testing Date(s) dead testing 26/10/2020 To 26/10/2020 Date(s) live testing 26/10/2020 To 26/10/2020 All electronic circuits Signature Tested by: Name (capital letters) Position Qualified Electricians Date 26/10/2020
Details of circuits and/or installed equipment vulnerable to damage when testing Date(s) dead testing 26/10/2020 To 26/10/2020
All electronic circuits
Tested by: Name (capital letters) Qualified Electricians Date 26/10/2020
Wiring Types. A PVC/PVC B PVC cables in metallic Conduit C PVC cables in non-metallic Conduit D PVC cables in metallic Trunking E PVC cables in non-metallic Trunking F PVC/SWA cables G SWA/XPLE cables H Mineral Insulated O Other
2 7 4 8 6 0 0 0 0 1 2 1
Page 6 of 7
Date(s) live testing 26/10/2020 To 26/10/2020
Signature
NA/ 2 7 4 8 6 0 0 0 0 1 2 1 9 EICR Page 7 of 7
CIRCUIT DETAILS TEST RESULTS
and Circuit Line No. No. Distribution board Designation Type of wiring Ref. method No. of points Circuit conductors csa (mm²) disconnection Maximum Overcurrent protective devices capacity Breaking operating RCD BS 7671 Max. permitted Zs Other 80% Circuit impedance Ω Insulation resistance (Record lower reading) Polarity Measured Max. Zs RCD testing Manual test button operation
DB1 L / N CPC Type No. Rating (A) Ring final circuits only (measured end-to-end) check Fig 8 All circuits to be completed using R1R2 or R2, not both Test voltage L/L, L/N L/E, N/E Above 30mA IΔn 30mA or below 5 IΔn RCD AFDD
Circuit designation BS EN Number (KA) (mA) (Ω) r1 rn r2 R1 + R2 R2 V M(Ω) M(Ω) (Ω) ms ms
7L2 Spare N/A N/A N/A N/A N/A N/A N/A
7L3 Spare N/A N/A N/A N/A N/A N/A N/A
8L1 Spare N/A N/A N/A N/A N/A N/A N/A
8L2 Spare N/A N/A N/A N/A N/A N/A N/A
8L3 Spare N/A N/A N/A N/A N/A N/A N/A
9L1 Spare N/A N/A N/A N/A N/A N/A N/A
9L2 Cloakroom lights A C 16 1.5 1.5 0.4 60898 B 6 10 300 5.82 N/A N/A N/A N/A 0.20 250 21.7 21.7 ü 0.47 289 ü N/A
9L3 Spare N/A N/A N/A N/A N/A N/A N/A
10L1 Spare N/A N/A N/A N/A N/A N/A N/A
10L2 Staff Downflow Heater A C 1 2.5 2.5 0.4 60898 B 10 10 300 3.49 N/A N/A N/A N/A 0.71 500 >1000 >1000 ü 0.36 289 ü N/A
10L3 Physio Office lights A C 5 1.5 1.5 0.4 60898 B 6 10 300 5.82 N/A N/A N/A N/A 0.65 250 266 266 ü 0.97 289 ü N/A
11L1 CR1 Bay 2 Heater A C 1 2.5 2.5 0.4 60898 B 16 10 300 2.18 N/A N/A N/A N/A 0.14 500 >1000 >1000 ü 0.73 289 ü N/A
11L2 Cloaks Downflow Heater A C 1 2.5 2.5 0.4 60898 B 10 10 300 3.49 N/A N/A N/A N/A 0.42 500 >1000 >1000 ü 0.84 289 ü N/A
11L3 Physio Office Heater A C 1 2.5 2.5 0.4 60898 B 16 10 300 2.18 N/A N/A N/A N/A 0.29 500 >1000 >1000 ü 0.73 289 ü N/A
12L1 CR1 Ring Main A C 2 2.5 2.5 0.4 61009 C 16 10 30 1.09 0.56 0.57 0.87 ü 0.39 250 14.6 14.6 ü 0.64 29.4 ü N/A
12L2 CR1 Water Heater A C 1 2.5 2.5 0.4 60898 B 16 10 300 2.18 N/A N/A N/A N/A 0.10 500 >1000 >1000 ü 0.64 289 ü N/A
12L3 Physio Office Ring Main A C 3 2.5 2.5 0.4 61009 C 16 10 30 1.09 0.72 0.74 1.14 ü 0.56 500 >1000 >1000 ü 0.68 29.4 ü N/A
Details of circuits and/or installed equipment vulnerable to damage when testing Date(s) dead testing 26/10/2020 To 26/10/2020 Date(s) live testing 26/10/2020 To 26/10/2020 All electronic circuits Signature Tested by: Name (capital letters) Position Qualified Electricians Date 26/10/2020 Wiring Types. A PVC/PVC B PVC cables in metallic Conduit C PVC cables in non-metallic Conduit D PVC cables in metallic Trunking E PVC cables in non-metallic Trunking F PVC/SWA cables G SWA/XPLE cables H Mineral Insulated O Other
Details of circuits and/or installed equipment vulnerable to damage when testing Date(s) dead testing 26/10/2020 To 26/10/2020
All electronic circuits
Tested by: Name (capital letters) Qualified Electricians Date 26/10/2020
Date(s) live testing 26/10/2020 To
Signature
Electrical Installation Condition Report Requirements for Electrical Installations - BS 7671:2018 (IET Wiring Regulations 18th Edition)
Information for recipients:
The purpose of this report is to confirm, so far as reasonably practicable, whether or not the electrical installation is in a satisfactory condition for continued service (see Section E). The report should identify any damage, deterioration, defects and/or conditions which may give rise to danger (see Section K). The person ordering the report should have received the original report and the inspector should have retained a duplicate. The original Report should be retained in a safe place and be made available to any person inspecting or undertaking work on the electrical installation in the future. If the property is vacated, this report will provide the new owner / occupier with details of the condition of the electrical installation at the time the report was issued. Where the installation incorporates residual current devices (RCDs) there should be a notice at or near the devices stating that they should be tested every 6 months. For safety reasons it is important that these instructions are followed. Section D (Extent and Limitations) should identify fully the extent of the installation covered by this report and any limitations on the inspection and testing. The Inspector should have agreed these aspects with the person ordering the report and with other interested parties (licencing authority, insurance company, mortgage provider and the like() before the inspection was carried out. Some operational limitations such as inability to gain access to parts of the installation or an item of equipment may have been encountered during the inspection. The inspector should have noted these in Section D. For items classified in Section K as C1 (“Danger Present”), the safety of those using the installation is at risk, and it is recommended that a skilled person or persons competent in electrical installation work undertakes the necessary remedial work immediately. For items classified in Section K as C2 (“Potentially Dangerous”), the safety of those using the installation may be at risk and it is recommended that a skilled person or persons competent in electrical installation work undertakes the necessary remedial work as a matter of urgency. Where it has been stated in Section K that an observation requires further investigation code FI the inspection has revealed an apparent deficiency which may result on a code C1 or C2 could not, due to the extent or limitations of this inspection, be fully identified. Such observations should be investigated as soon as possible. A further examination of the installation will be necessary, to determine the nature and extent of the apparent deficiency (see Section F). For safety reasons, the electrical installation should be re-inspected at appropriate intervals by a skilled person or persons competent in such work. The recommended date by which the next inspection is due is stated in Section F of the report under ‘Recommendations’ and on label at or near to the consumer unit/distribution board.
2 7 4 8 6 0 0 0 0 1 2 2 0
Page 2 of 6
A Details of the Installation
Client Public Estates and Housing Division Installation
Address Department of Infrastructure Hills Meadow Peel Road Douglas Isle of Man Address Castle Rushen High School Mobile Two Arbory Road Castletown
Postcode IM1 5EB Postcode IM9 1RE
B Reason for producing this report This form is to be used only for reporting on the condition of an existing installation.
Periodic Inspection and Test of Electrical Installation
Date(s) on which the inspection and testing were carried out 26 /10/2020 to 26/10/2020
C Details of installation which is the subject of this report
Description of premises Domestic Commercial
Estimated age of the wiring system 18 years
Evidence of alterations or addition Yes No Not apparent if 'Yes', estimated 10 years
Records of installation available Yes No Records held by NA
Date of last inspection Not Known Electrical Installation Certificate No. or previous Inspection Report No. N/A
D Extent of electrical installation covered by this report: Agreed Limitations and Operational Limitations (Regulations 653.2)
100% of circuits None
Operational limitations including the reasons see page no 1 Agreed with: NA
The inspection and testing detailed within this report and accompanying schedule has been carried out in accordance with BS 7671: 2018 amended to 2019
It should be noted that cables concealed within trunkings and conduits, under floors, in roof spaces and generally within the fabric of the building or underground have not been inspected unless specifically agreed between the client and inspector prior to the inspection. An inspection should be made within an accessible roof space housing other electrical equipment.
E
General conditions of the installation (in terms of safety)
Suitable for continued use.
Overall assessment of the installation in terms of its suitability for continued use SATISFACTORY *UNSATISFACTORY
F Recommendations
Where the overall assessment of the suitability of the installation for continued use above is stated as UNSATISFACTORY I/we recommend that any observations classified as ‘Danger present’ (code C1) or ‘Potential dangerous’ (code C2) are acted upon as a matter of urgency. Investigation without delay is recommended for observations identified as ‘Further Investigation required’ (code FI). Observations classified as ‘Improvement recommended’ (code C3) should be given due
consideration. Subject to the necessary remedial action being taken, I/we recommend that the installation is further inspected and tested by 26/10/2025 (date)
G Declaration
I/we being the person(s) responsible for the inspection and the testing of the electrical installation (as indicated by my/our signatures below), particulars of which are described above, having exercised reasonable skill and care when carrying out the inspection and testing hereby declare that the information in this report, including the observations and the attached schedules, provides an accurate assessment of the condition of the electrical installation taking into account the stated extent and limitations in section D of this report.
Company Inspected and tested by Authorised for issue by
Membership No. Name:
Address Signature:
Position:
Postcode Date:
H Schedule(s)
1 schedule(s) of inspection and 1 schedule(s) of test results are attached.
The attached schedule(s) are part of this document and this report is valid only when they are attached to it.
2 7 4 8 6 0 0 0 0 1 2 2 0
Page 3 of 6
I Supply characteristics and earthing arrangements
Earthing Arrangements
Number & Type of live conductors
TN-S
AC DC
TT
No. of phases 3
Please specify
No. of wires 4
Nature of Supply Parameters (Note: (1) by enquiry, (2) by enquiry or by measurement)
Nominal voltage, U/U0 (1) 400 v Nominal frequency, f(1) 50 H
Prospective fault current, Ipf (2) 1.17 kA 0.34 Ω Or Zdb Source of Circuit
Supply Protective Device BS (EN) 60898 Type 2 Rated Current 63 A
Other Sources of Supply (as detailed on attached schedule)
J Particulars of installation referred to in this report
Details of installation Earth Electrode (where applicable) Type (e.g. rod(s), tape etc ) N/A
Location N/A Electrode resistance to ear th N/A Ω Distributors facility Installation Earth Electrode
Main Protective Conductors Material csa ( ü) or Value Maximum Demand (load) N/A Amps KVA
Earthing Conductor Copper 16 Ω (connection / continuity) ( ü)or Value (ü) or Value
Protective Bonding Conductor (to extraneous-conductive-parts) Copper Water installation Ω To structural steel Ω
Gas installation pipes Ω To lightning protection Ω
Main Supply Conductor Copper Oil installation pipes Ω Othe r Ω
Main Switch Location
Fuse/device rating or setting 63 A Voltage rating 400 V
If RCD main switch: Rated residual operating current I Δn mA
60898 N o. of Poles 3
Rated time delay m
Current Rating 63 A
Measured operating trip time ms
Observations
Referring to the attached schedule of inspection and test results, and subject to the limitations at Section D.
No remedial work required
Danger present. Risk of Injury. Immediate remedial action required.
Potentially dangerous. Urgent remedial action required.
Improvement recommended.
Further Investigation required without delay
Item No. Observations Code
1 DB1 6L3 - socket is directly above the cooker within 300mm.
One of the above codes, as appropriate, has been allocated to each of the observations made above and/or any attached observation sheets to indicate to the person(s) responsible for the installation the degree of urgency for remedial action. Danger present. Risk of Injury. Immediate remedial action required. Potentially dangerous. Urgent remedial action required. Improvement recommended. 1 Further Investigation required without delay
Danger present. Risk of Injury. Immediate remedial action required.
Potentially dangerous. Urgent remedial action required.
Improvement recommended. 1
Further Investigation required without delay
2 7 4 8 6 0 0 0 0 1 2 2 0
Page 4 of 6
Outcomes
Acceptable condition: Unacceptable condition: State Improvement recommended: Further Investigation: Not Verified: Limitation: Not Applicable:
or
In the outcome column use the codes above. Provide additional comment where appropriate. C1/C2/C3 and FI coded items to be recorded in section K of the condition report.
Item No. Description Outcome
1.0 External Condition Of Intake Equipment (Visual Inspection Only) Where inadequacies are encountered, it is recommended that the person ordering the report informs the appropriate authority 1.1 Service cable 1.2 Service head 1.3 Earthing arrangement 1.4 Meter tails 1.5 Metering equipment 1.6 Isolator (where present) 2.0 Presence Of Adequate Arrangements For Other Sources Such As Microgenerators (551.6; 551.7) 3.0 Earthing / Bonding Arrangements (411.3; Chap 54) 3.1 Presence and condition of distributor’s earthing arrangement (542.1.2.1; 542.1.2.2) 3.2 Presence and condition of earth electrode connection where applicable (542.1.2.3) 3.3 Provision of earthing/bonding labels at all appropriate locations (514.13.1) 3.4 Confirmation of earthing conductor size (542.3; 543.1.1) 3.5 Accessibility and condition of earthing conductor at MET arrangement (543.3.2) 3.6 Confirmation of main protective bonding conductor sizes (544.1) 3.7 Condition and accessibility of main protective bonding conductor/connections (543.3.2; 544.1.2) 3.8 Accessibility and condition of other protective bonding connections (543.3.1; 543.3.2) 4.0 Consumer Unit(s) / Distribution Board(s) 4.1 Adequacy of working space/accessibility to consumer unit/distribution board (132.12; 513.1) 4.2 Security of fixing (134.1.1) 4.3 Condition of enclosure(s) in terms of IP rating etc (416.2) 4.4 Condition of enclosure(s) in terms of fire rating etc (421.1.201; 526.5) 4.5 Enclosure not damaged/deteriorated so as to impair safety (651.2) 4.6 Presence of main linked switch (as required by 462.1.201) 4.7 Operation of main switches (functional check) (643.10) 4.8 Manual operation of circuit-breakers and RCD(s) to prove disconnection (643.10) 4.9 Correct identification of circuit details and protective devices (514.8.1; 514.9.1) 4.10 Presence of RCD six-monthly test notice at or near consumer unit/distribution board (514.12.2) 4.11 Presence of non-standard (mixed) cable colour warning notice at or near consumer unit/distribution board (514.14) 4.12 Presence of alternative supply warning notice at or near consumer unit/distribution board (514.15) 4.13 Presence of other required labelling (please specify) (Section 514) Compatibility of protective devices, bases and other components; correct type and rating (No signs of unacceptable thermal 4.14 damage, arcing or overheating) (411.3.2; 411.4; 411.5; 411.6; section 432.433) 4.15 Single-pole switching or protective devices in line conductor only (132.14.1; 530.3.3) Protection against mechanical damage where cables enter consumer unit/distribution board (132.14.1; 522.8.1; 522.8.5; 4.16 522.8.11) 4.17 Protection against electromagnetic effects where cables enter consumer unit/distribution board/enclosures (521.5.1) 4.18 RCD(s) provided for fault protection - includes RCBOs (411.4.204; 411.5.2; 531.2) 4.19 RCD(s) provided for additional protection / requirements - includes RCBOs (411.3.3; 415.1) 4.20 Confirmation of indication that SPD is functional (651.4) Confirmation that ALL conductor connections, including connections to busbars, are correctly located in terminals and are 4.21 tight and secure (526.1) 4.22 Adequate arrangements where a generating set operates as a switched alternative to the public supply (551.6) 4.23 Adequate arrangements where a generating set operates in parallel with the public supply (551.7) 5.0 Final Circuits 5.1 Identification of conductors (514.3.1) 5.2 Cables correctly supported throughout their run (521.10.202; 522.8.5) 5.3 Condition of insulation of live parts (416.1) 5.4 Non-sheathed cables protected by enclosure in conduit, ducting or trunking. Integrity of containment (521.10.1) 5.4.1 To include the integrity of conduit and trunking systems (metallic and plastic) 5.5 Adequacy of cables for current-carrying capacity with regard for the type and nature of installation (Section 523) 5.6 Coordination between conductors and overload protective devices (433.1; 533.2.1) 5.7 Adequacy of protective devices: type and rated current for fault protection (411.3) 5.8 Presence and adequacy of circuit protective conductors (433.3.1; Section 543) 5.9 Wiring system(s) appropriate for the type and nature of the installation and external influences (Section 522)
1.0 External Condition Of Intake Equipment (Visual Inspection Only) Where inadequacies are encountered, it is recommended that the person ordering the report informs the appropriate authority
1.1 Service cable
1.2 Service head
1.3 Earthing arrangement
1.4 Meter tails
1.5 Metering equipment
1.6 Isolator (where present)
2.0 Presence Of Adequate Arrangements For Other Sources Such As Microgenerators (551.6; 551.7)
3.0 Earthing / Bonding Arrangements (411.3; Chap 54)
3.1 Presence and condition of distributor’s earthing arrangement (542.1.2.1; 542.1.2.2)
3.2 Presence and condition of earth electrode connection where applicable (542.1.2.3)
3.3 Provision of earthing/bonding labels at all appropriate locations (514.13.1)
3.4 Confirmation of earthing conductor size (542.3; 543.1.1)
3.5 Accessibility and condition of earthing conductor at MET arrangement (543.3.2)
3.6 Confirmation of main protective bonding conductor sizes (544.1)
3.7 Condition and accessibility of main protective bonding conductor/connections (543.3.2; 544.1.2)
3.8 Accessibility and condition of other protective bonding connections (543.3.1; 543.3.2)
4.0 Consumer Unit(s) / Distribution Board(s)
4.1 Adequacy of working space/accessibility to consumer unit/distribution board (132.12; 513.1)
4.2 Security of fixing (134.1.1)
4.3 Condition of enclosure(s) in terms of IP rating etc (416.2)
4.4 Condition of enclosure(s) in terms of fire rating etc (421.1.201; 526.5)
4.5 Enclosure not damaged/deteriorated so as to impair safety (651.2)
4.6 Presence of main linked switch (as required by 462.1.201)
4.7 Operation of main switches (functional check) (643.10)
4.8 Manual operation of circuit-breakers and RCD(s) to prove disconnection (643.10)
4.9 Correct identification of circuit details and protective devices (514.8.1; 514.9.1)
4.10 Presence of RCD six-monthly test notice at or near consumer unit/distribution board (514.12.2)
4.11 Presence of non-standard (mixed) cable colour warning notice at or near consumer unit/distribution board (514.14)
4.12 Presence of alternative supply warning notice at or near consumer unit/distribution board (514.15)
4.13 Presence of other required labelling (please specify) (Section 514)
4.14 Compatibility of protective devices, bases and other components; correct type and rating (No signs of unacceptable thermal damage, arcing or overheating) (411.3.2; 411.4; 411.5; 411.6; section 432.433)
4.15 Single-pole switching or protective devices in line conductor only (132.14.1; 530.3.3)
4.16 Protection against mechanical damage where cables enter consumer unit/distribution board (132.14.1; 522.8.1; 522.8.5; 522.8.11)
4.17 Protection against electromagnetic effects where cables enter consumer unit/distribution board/enclosures (521.5.1)
4.18 RCD(s) provided for fault protection - includes RCBOs (411.4.204; 411.5.2; 531.2)
4.19 RCD(s) provided for additional protection / requirements - includes RCBOs (411.3.3; 415.1)
4.20 Confirmation of indication that SPD is functional (651.4)
4.21 Confirmation that ALL conductor connections, including connections to busbars, are correctly located in terminals and are tight and secure (526.1)
4.22 Adequate arrangements where a generating set operates as a switched alternative to the public supply (551.6)
4.23 Adequate arrangements where a generating set operates in parallel with the public supply (551.7)
5.0 Final Circuits
5.1 Identification of conductors (514.3.1)
5.2 Cables correctly supported throughout their run (521.10.202; 522.8.5)
5.3 Condition of insulation of live parts (416.1)
5.4 Non-sheathed cables protected by enclosure in conduit, ducting or trunking. Integrity of containment (521.10.1)
5.4.1 To include the integrity of conduit and trunking systems (metallic and plastic)
5.5 Adequacy of cables for current-carrying capacity with regard for the type and nature of installation (Section 523)
5.6 Coordination between conductors and overload protective devices (433.1; 533.2.1)
5.7 Adequacy of protective devices: type and rated current for fault protection (411.3)
5.8 Presence and adequacy of circuit protective conductors (433.3.1; Section 543)
5.9 Wiring system(s) appropriate for the type and nature of the installation and external influences (Section 522)
reated by NAPIT Desktop © Copyright 2020 Page 4 of 6 th Floor, Mill 3, Pleasley Vale Business Park, Mansfield, Nottinghamshire NG19 8RL NA/EICR/001
Electrical Installation Condition Report Inspection Schedule for Domestic and Similar Premises up to 100 A NA/ 2 7 4 8 6 0 0 0 0 1 2 2 0 Requirements for Electrical Installations - BS 7671:2018 (IET Wiring Regulations 18th Edition) All items inspections to confirm as EICR Page 5 of 6 appropriate, compliance with the relevant clauses in BS 7671:2018 5.10 Concealed cables installed in prescribed zones (see Section D. Extent and limitations) (522.6.202) Cables concealed under floors, above ceilings or in walls/partitions, adequately protected against damage (see Section D. 5.11 Extent and limitations) (522.6.204) 5.12 Provision of additional requirements for protection by RCD not exceeding 30 mA 5.12.1 for all socket-outlets of rating 32 A or less, unless an exception is permitted (411.3.3) 5.12.2 For the supply of mobile equipment not exceeding 32 A rating for use outdoors (411.3.3) 5.12.3 for cables concealed in walls at a depth of less than 50 mm (522.6.202; 522.6.203) 5.12.4 for cables concealed in walls/partitions containing metal parts regardless of depth (522.6.203) 5.12.5 for circuits supplying luminaires within domestic (household) premises (411.3.4) 5.13 Provision of fire barriers, sealing arrangements and protection against thermal effects (Section 527) 5.14 Band II cables segregated/separated from Band I cables (528.1) 5.15 Cables segregated/separated from communications cabling (528.2) 5.16 Cables segregated/separated from non-electrical services (528.3) 5.17 Termination of cables at enclosures - indicate extent of sampling in Section D of the report (Section 526) 5.17.1 Connections soundly made and under no undue strain (526.6) 5.17.2 No basic insulation of a conductor visible outside enclosure (526.8) 5.17.3 Connections of live conductors adequately enclosed (526.5) 5.17.4 Adequately connected at point of entry to enclosure (glands, bushes etc.) (522.8.5) 5.18 Condition of accessories including socket-outlets, switches and joint boxes (651.2(v)) 5.19 Suitability of accessories for external influences (512.2) 5.20 Adequacy of working space/accessibility to equipment (132.12; 513.1) 5.21 Single-pole switching or protective devices in line conductors only (132.14.1, 530.3.3) 6.0 Location(s) Containing A Bath Or Shower 6.1 Additional protection for all low voltage (LV) circuits by RCD not exceeding 30 mA (701.411.3.3) 6.2 Where used as a protective measure, requirements for SELV or PELV met (701.414.4.5) 6.3 Shaver sockets comply with BS EN 61558-2-5 formerly BS 3535 (701.512.3) 6.4 Presence of supplementary bonding conductors, unless not required by BS 7671:2018 (701.415.2) 6.5 Low voltage (e.g. 230 volt) socket-outlets sited at least 3 m from zone 1 (701.512.3) 6.6 Suitability of equipment for external influences for installed location in terms of IP rating (701.512.2) 6.7 Suitability of accessories and controlgear etc. for a particular zone (701.512.3) 6.8 Suitability of current-using equipment for particular position within the location (701.55) 7.0 Other Part 7 Special Installations Or Locations 7.01 List all other special installation or locations, if any (record seperately the results of particular inspections applied).
5.10 Concealed cables installed in prescribed zones (see Section D. Extent and limitations) (522.6.202)
5.11 Cables concealed under floors, above ceilings or in walls/partitions, adequately protected against damage (see Section D. Extent and limitations) (522.6.204)
5.12 Provision of additional requirements for protection by RCD not exceeding 30 mA
5.12.1 for all socket-outlets of rating 32 A or less, unless an exception is permitted (411.3.3)
5.12.2 For the supply of mobile equipment not exceeding 32 A rating for use outdoors (411.3.3)
5.12.3 for cables concealed in walls at a depth of less than 50 mm (522.6.202; 522.6.203)
5.12.4 for cables concealed in walls/partitions containing metal parts regardless of depth (522.6.203)
5.12.5 for circuits supplying luminaires within domestic (household) premises (411.3.4)
5.13 Provision of fire barriers, sealing arrangements and protection against thermal effects (Section 527)
5.14 Band II cables segregated/separated from Band I cables (528.1)
5.15 Cables segregated/separated from communications cabling (528.2)
5.16 Cables segregated/separated from non-electrical services (528.3)
5.17 Termination of cables at enclosures - indicate extent of sampling in Section D of the report (Section 526)
5.17.1 Connections soundly made and under no undue strain (526.6)
5.17.2 No basic insulation of a conductor visible outside enclosure (526.8)
5.17.3 Connections of live conductors adequately enclosed (526.5)
5.17.4 Adequately connected at point of entry to enclosure (glands, bushes etc.) (522.8.5)
5.18 Condition of accessories including socket-outlets, switches and joint boxes (651.2(v))
5.19 Suitability of accessories for external influences (512.2)
5.20 Adequacy of working space/accessibility to equipment (132.12; 513.1)
5.21 Single-pole switching or protective devices in line conductors only (132.14.1, 530.3.3)
6.0 Location(s) Containing A Bath Or Shower
6.1 Additional protection for all low voltage (LV) circuits by RCD not exceeding 30 mA (701.411.3.3)
6.2 Where used as a protective measure, requirements for SELV or PELV met (701.414.4.5)
6.3 Shaver sockets comply with BS EN 61558-2-5 formerly BS 3535 (701.512.3)
6.4 Presence of supplementary bonding conductors, unless not required by BS 7671:2018 (701.415.2)
6.5 Low voltage (e.g. 230 volt) socket-outlets sited at least 3 m from zone 1 (701.512.3)
6.6 Suitability of equipment for external influences for installed location in terms of IP rating (701.512.2)
6.7 Suitability of accessories and controlgear etc. for a particular zone (701.512.3)
6.8 Suitability of current-using equipment for particular position within the location (701.55)
7.0 Other Part 7 Special Installations Or Locations
7.01 List all other special installation or locations, if any (record seperately the results of particular inspections applied).
8.0 Schedule of Tests Results to be recorded on Schedule of Test Results
8.1 External earth loop impedance, Ze
8.2 Installation earth electrode
8.3 Prospective fault current, lpf
8.4 Continuity of Earth Conductors
8.5 Continuity of Circuit Protective Conductors
8.6 Continuity of ring final circuit
8.7 Continuity of Protective Bonding Conductors
8.8 Volt drop verified
2 7 4 8 6 0 0 0 0 1 2 2 0
Page 5 of 6
8.9 Insulation Resistance between Live Conductors
8.10 Insulation Resistance between Live Conductors & Earth
8.11 Polarity (prior to energisation)
8.12 Polarity (after energisation) including phase sequence
8.13 Earth Fault Loop Impedance
8.14 RCDs / RCBOs including selectivity
8.15 Functional testing of RCD devices
8.16 Functional testing of AFDD(s) devices
NA/ 2 7 4 8 6 0 0 0 0 1 2 2 0 EICR Page 6 of 6
Client Public Estates and Housing Division Installation Address Castle Rushen High School, Castletown Postcode IM9 1RE
Distribution board details - Complete in every case Complete only if the distribution board is not connected directly to the origin of the installation Test instrument serial number(s)
Location Storeroom Designation DB1 Supply to distribution board is from Overcurrent No. of phases Mains Intake protective device 3 Type2 BS(EN) 60898 for the distribution circuit: Nominal Voltage Rating63 400 Supply polarity confirmed Phase sequence confirmed A 2 A Z I Ti Characteristics at this distribution board ssociated RCD(if any): BS (EN) Above 30mA 3227 Operating at 1 IΔn289 ms (if appli Loop impedance Insulation resistance Continuity C10066 C10066 C10066
Num. of ways 18 d0.26 Ω No. of poles2 30mA or below cable) pf 1.77 kA Operating at 5 IΔn ms IΔn me delay (if applicable) RCDC10066
CIRCUIT DETAILS TEST RESULTS
and Circuit Line No. No. Distribution board Designation Type of wiring Ref. method No. of points Circuit conductors csa (mm²) disconnection Maximum Overcurrent protective devices capacity Breaking operating RCD BS 7671 Max. permitted Zs Other 80% Circuit impedance Ω Insulation resistance (Record lower reading) Polarity Measured Max. Zs RCD testing Manual test button operation
DB1 L / N CPC Type No. Rating (A) Ring final circuits only (measured end-to-end) check Fig 8 All circuits to be completed using R1R2 or R2, not both Test voltage L/L, L/N L/E, N/E Above 30mA IΔn 30mA or below 5 IΔn RCD AFDD
Circuit designation BS EN Number (KA) (mA) (Ω) r1 rn r2 R1 + R2 R2 V M(Ω) M(Ω) (Ω) ms ms
1L1 Contactor Control A C 1 1.5 1 0.4 60898 B 6 10 5.82 N/A N/A N/A N/A 0.15 250 >1000 >1000 ü 0.65 N/A N/A
1L2 C R Row 1 Lights A C 8 1.5 1 0.4 60898 B 6 10 5.82 N/A N/A N/A N/A 0.18 250 263 263 ü 0.93 N/A N/A
1L3 C R Heater A C 2 2.5 1.5 0.4 60898 B 16 10 2.18 N/A N/A N/A N/A 0.04 500 >1000 >1000 ü 0.75 N/A N/A
2L1 Lobby,WC,Store,Quiet Rm lights A C 9 1.5 1 0.4 60898 B 6 10 5.82 N/A N/A N/A N/A 0.37 250 373 373 ü 0.98 N/A N/A
2L2 Field Wall Trunking sockets A C 4 2.5 1.5 0.4 61009 C 32 10 30 0.54 0.12 0.12 0.15 ü 0.24 500 >1000 >1000 ü 0.44 39.9 ü N/A
2L3 Cooker A C 1 6 2.5 0.4 61009 C 32 10 30 0.54 N/A N/A N/A N/A 0.31 500 >1000 >1000 ü 0.70 28.8 ü N/A
3L1 Water Heater A C 1 2.5 1.5 0.4 60898 B 16 10 2.18 N/A N/A N/A N/A 0.34 500 >1000 >1000 ü 0.68 N/A N/A
3L2 Quiet Rm sockets A C 2 2.5 1.5 0.4 61009 C 16 10 30 1.09 0.10 0.09 0.14 ü 0.32 500 >1000 >1000 ü 0.57 10.4 ü N/A
3L3 CR socket A C 1 2.5 1.5 0.4 61009 C 16 10 30 1.09 0.08 0.08 0.12 ü 0.31 500 >1000 >1000 ü 0.52 29.9 ü N/A
4L1 Cold Watcher A C 1 1.5 1 0.4 60898 B 6 10 5.82 N/A N/A N/A N/A 0.14 500 >1000 >1000 ü 0.58 N/A N/A
4L2 Quiet Rm Heater socket A C 1 2.5 1.5 0.4 60898 B 16 10 2.18 N/A N/A N/A N/A 0.12 500 >1000 >1000 ü 0.61 N/A N/A
4L3 I T Spur A C 1 2.5 1.5 0.4 60898 B 16 10 2.18 N/A N/A N/A N/A 0.04 500 >1000 >1000 ü 0.56 N/A N/A
5L1 Hand Dryer A C 1 2.5 1.5 0.4 60898 B 16 10 2.18 N/A N/A N/A N/A 0.18 500 >1000 >1000 ü 0.61 N/A N/A
5L2 Trunking sockets A C 4 2.5 1.5 0.4 61009 C 32 10 30 0.54 0.19 0.19 0.24 ü 0.26 500 >1000 >1000 ü 0.68 16.5 ü N/A
5L3 Store Rm sockets A C 2 2.5 1.5 0.4 60898 B 16 10 2.18 N/A N/A N/A N/A 0.15 500 >1000 >1000 ü 0.49 N/A N/A
6L1 Store Rm Water Heater A C 1 2.5 1.5 0.4 60898 B 16 10 2.18 N/A N/A N/A N/A 0.12 500 >1000 >1000 ü 0.51 N/A N/A
6L2 Cooker A C 1 6 2.5 0.4 61009 C 32 10 30 0.54 N/A N/A N/A N/A 0.22 500 >1000 >1000 ü 0.77 28.8 ü N/A
6L3 Kitchen sockets & spur A C 5 2.5 1.5 0.4 61009 C 32 10 30 0.54 0.37 0.37 0.56 ü 0.32 500 >1000 >1000 ü 0.71 24.3 ü N/A
Details of circuits and/or installed equipment vulnerable to damage when testing Date(s) dead testing 26/10/2020 To 26/10/2020 Date(s) live testing 26/10/2020 To 26/10/2020 All electronic circuits Signature Tested by: Name (capital letters) Position Qualified Electricians Date 26/10/2020
Details of circuits and/or installed equipment vulnerable to damage when testing Date(s) dead testing 26/10/2020 To 26/10/2020
All electronic circuits
Tested by: Name (capital letters) Qualified Electricians Date 26/10/2020
Wiring Types. A PVC/PVC B PVC cables in metallic Conduit C PVC cables in non-metallic Conduit D PVC cables in metallic Trunking E PVC cables in non-metallic Trunking F PVC/SWA cables G SWA/XPLE cables H Mineral Insulated O Other
2 7 4 8 6 0 0 0 0 1 2 2
Page 6 of 6
Date(s) live testing 26/10/2020 To 26/10/2020
Signature

Full Response Text

001 December 2016 Contents 1. Introduction 2. Suitability survey results Administration English Science Maths Languages Geography History 6th Form ICT Art D&T Drama Music Library PE SEN Corridors Catering Site 3. Building zones 4. Traffic 5. DDA 6. Conclusion Appendix 1 – Methodology 2 ϭ͘ /ŶƚƌŽĚƵĐƚŝŽŶ This Suitability Study has been undertaken to inform the business case for the replacement of the existing school. The study considers the suitability of the principal spaces with in the school building in terms of their effect on teaching, moral and behaviour. The methodology behind the study is attached as Appendix 1. Ϯ͘ ^ƵŝƚĂďŝůŝƚLJ ^ƚƵĚLJ ZĞƐƵůƚƐ The report results are set out below by department/use. 3 Spaces Direct Impact on Education H & S/ Security Disabled Access Comments Typ Category School Room Ref Room Asset Code Size/Shape Environment Location Fixed Furniture ICT Infrastructure A B C D High Medium Low Yes No Admin corridor A103 0 0 0 0 0 Storage of items awaiting pickup due to lack of storage. Doors off to accommodation are narrower than required by current legislation. General office A105 1 Awkward shape for furniture layout. 1 Cold in winter as door to reception is open due to restricted layout. 0 0 1 Lack of data and power sockets. Storage of items awaiting pickup due to lack of storage. Access doors are narrower than required by current legislation. Office A106 0 2 No direct daylight or natural ventilation. 0 0 0 Electronic door lock due to storage of sensitive information. Access doors are narrower than required by current legislation. 5 Spaces Direct Impact on Education H & S/ Security Disabled Access Comments Typ Category School Room Ref Room Asset Code Size/Shape Environment Location Fixed Furniture ICT Infrastructure A B C D High Medium Low Yes No Male staff toilet A107 0 0 0 0 0

Disabled toilet provision adjacent. Photo copier A108 1

Small room with inadequate space for materials and personnel. 1

Minimal mechanical ventilation. Hot in summer. 0 0 0

Congested space.

Access door is narrower than required by current legislation. No space to manoeuvre.
Store A109 0 0 0 0 0

Narrow door width does not comply with current requirements for wheelchair access. 6 Spaces Direct Impact on Education H & S/ Security Disabled Access Comments Typ Category School Room Ref Room Asset Code Size/Shape Environment Location Fixed Furniture ICT Infrastructure A B C D High Medium Low Yes No Office
A110 0 0 0 0 0

Narrow door width does not comply with current requirements for wheelchair access. Female staff toilet A111 0 0 0 0 0

Disabled toilet adjacent. Deputy Head’s office A112 0 0 0 0 0

Narrow door width does not comply with current requirements for wheelchair access. 7 Spaces Direct Impact on Education H & S/ Security Disabled Access Comments Typ Category School Room Ref Room Asset Code Size/Shape Environment Location Fixed Furniture ICT Infrastructure A B C D High Medium Low Yes No Disabled toilet A113 0 0 0 0 0

Narrow door width does not comply with current requirements for wheelchair access. Deputy Head’s office A114 0 0 0 0 0

Narrow door width does not comply with current requirements for wheelchair access. Head Teacher’s office A115 1

Room’s poor shape limits furniture layout options. 0 0 0 0

Narrow door width does not comply with current requirements for wheelchair access. 8 Spaces Direct Impact on Education H & S/ Security Disabled Access Comments Typ Category School Room Ref Room Asset Code Size/Shape Environment Location Fixed Furniture ICT Infrastructure A B C D High Medium Low Yes No Office A116 0 1

Area generally lacking heating. 2

No disabled access from main school accommodation. 0 0

Access door is narrower than required by current legislation. Access for wheelchair bound person requires them to exit the school and re-enter adjacent to this room due to stairs in corridor from admin area
Corridor A119 0 0 2

No disabled access from main school accommodation. 0 0

No disabled access from within main school building. Office Listening A120 0 0 2

No disabled access from main school accommodation. 0 0

Narrow door width does not comply with current requirements for wheelchair access. 9 Spaces Direct Impact on Education H & S/ Security Disabled Access Comments Typ Category School Room Ref Room Asset Code Size/Shape Environment Location Fixed Furniture ICT Infrastructure A B C D High Medium Low Yes No Toilet A122 0 0 0 0 0

No disabled toilet provision on this level. Medical room A124 0 1 Area generally lacking heating. 2

No disabled access to medical room without having to exit the main building and re-enter. 0 0

Access door is narrower than required by current legislation. Access for wheelchair bound person requires them to exit the school and re-enter adjacent to this room due to stairs in corridor from admin area.
Corridor A125 0 0 0 0 0

10 Spaces Direct Impact on Education H & S/ Security Disabled Access Comments Typ Category School Room Ref Room Asset Code Size/Shape Environment Location Fixed Furniture ICT Infrastructure A B C D High Medium Low Yes No Staffroom
A127 1

Not sufficiently large to comfortably allow full staff meetings. 0 1

Remote from remainder of school. Not heavily utilised. 0 1

Lack of data and power outlets.

Narrow door width does not comply with current requirements for wheelchair access. Stair A125 0 0 0 0 0

No disabled access to the upper floor meeting rooms. Kitchen A461 0 0 0 0 0

Narrow door width does not comply with current requirements for wheelchair access. 11 Spaces Direct Impact on Education H & S/ Security Disabled Access Comments Typ Category School Room Ref Room Asset Code Size/Shape Environment Location Fixed Furniture ICT Infrastructure A B C D High Medium Low Yes No Conference room A462a 0 ? 2

No disabled access to this level. 0 ?

No disabled access to this level. Meeting room A426 0 ? 2

No disabled access to this level. 0 ?

No disabled access to this level. 12 Synopsis – Initial impression of school entrance area is of sporadic clutter and of the reception area being primarily a circulation space – access to dining, main hall, administration area and upper floor all from the reception/entrance space. The main school entrance is used for reception of visitors, staff, students, deliveries of stationery and frozen food for the kitchen. There is no dedicated visitor meeting room, with the result that visitors are taken to the far end of the admin area, past offices and potentially sensitive areas. The primary meeting and conference rooms are on the first floor in an area not served by lift and thus not readily accessible by the disabled. There is a marked and severe lack of storage for files and records in the administration area resulting in filing cabinets and other storage vessels being located in corridors throughout the school.
13 Spaces Direct Impact on Education H & S/ Security Disabled Access Comments Type Category Unique Room Ref Room Designation Code Size/Shape Environment Location Fixed Furniture ICT Infrastructure A B C D High Medium Low Yes No Class 3 R161 2

Room size well below recommended standard class area (BB98) 0 0 2

Student lockers in classroom, reduce space, access difficulties, lack of use. 0

Lockers access and lack of space for disabled

Narrow door does not comply with current requirements. Class 4 R163 1 Room area marginal. 0 0 2

Student lockers in classroom, reduce space, access difficulties, lack of use. 0

Lockers access and lack of space for disabled

Narrow door does not comply with current requirements. Office
5 R167 0 0 0 0

Narrow door does not comply with current requirements. 0 15 Spaces Direct Impact on Education H & S/ Security Disabled Access Comments Type Category Unique Room Ref Room Designation Code Size/Shape Environment Location Fixed Furniture ICT Infrastructure A B C D High Medium Low Yes No Class 6 R181 2 Room size well below recommended standard class area (BB98) 0 0 2 Student lockers in classroom, reduce space, access difficulties, lack of use. 0

Lockers access and lack of space for disabled

Narrow door does not comply with current requirements. Class 7 R183 1 Room area marginal. 0 0 2 Student lockers in classroom, reduce space, access difficulties, lack of use. 0

Lockers access and lack of space for disabled

Narrow door does not comply with current requirements. Synopsis – All classrooms below areas recommended by BB 98. Issue exacerbated by the location of student lockers in most of the classrooms. These are generally unused as access and space around them is very restricted. All rooms in close proximity. Narrow corridors outside all rooms. 16 Castle Rushen High School Accommodation suitability study Survey Form Assessment Date 8th November 2016 Science Assessed by - School rep – Spaces Direct Impact on Education H & S/ Security Disabled Access Comments Type Category Unique Room Ref Room Designation Code Size/Shape Environment Location Fixed Furniture ICT Infrastructure A B C D High Medium Low Yes No Lab 1 L405 0/1

Room area marginal. 1

No blackout provision limits experiments. Mechanical vent. 2

At extreme end of ‘string’ of science labs, poor relationship to resources and Science staff facilities. Lack of prep room. 1

Fixed furniture layout restricts flexibility and supervision. Fume cupboards against wall limits visibility of experiments by students. 0 WIFI enabled

Single means of escape from room

Narrow door does not meet current requirements. Access by way of poor quality lift opening directly into Lab 2 Lan 1x L407 0/1 Small group room. 0 2 At extreme end of ‘string’ of science labs, poor relationship to resources and Science staff facilities. 0 0 WIFI enabled

Single means of escape from room if used for experiments.

Narrow door does not meet current requirements. Access by way of poor quality lift opening directly into Lab 2 17 Spaces Direct Impact on Education H & S/ Security Disabled Access Comments Type Category Unique Room Ref Room Designation Code Size/Shape Environment Location Fixed Furniture
ICT Infrastructure A B C D High Medium Low Yes No Lab 2 L406 0/1

Room area marginal. 1

No blackout provision limits experiments. No mechanical vent. 1

Poor relationship to Science staff facilities. 1

Fixed furniture layout restricts flexibility and supervision. Fume cupboards against wall limits visibility of experiments by students. 0 WIFI enabled

Ramped floor at main access to lab. Second escape through chemical store/prep room.

Access by way of poor quality lift opening directly into Lab 2 Lab 2x L404 0/1 Small group room set up as computer room. 1 Poor ventilation 1 Poor relationship to Science staff facilities. 0 0

Narrow door does not meet current requirements. Access by way of poor quality lift opening directly into Lab 2 Prep 2/3 L408 0 1 Poor ventilation 0 0 0

Lab 3 and 4 second means of escape is through the prep area, potentially impeded by furniture and equipment.

Narrow door does not meet current requirements. Access by way of poor quality lift opening directly into Lab 2 18 Spaces Direct Impact on Education H & S/ Security Disabled Access Comments Type Category Unique Room Ref Room Designation Code Size/Shape Environment Location Fixed Furniture
ICT Infrastructure A B C D High Medium Low Yes No Lab 3 L410 0/1

Room area marginal. 1

No blackout provision limits experiments. No mechanical ventilation. 1

Poor relationship to Science staff facilities. 1

Fixed furniture layout restricts flexibility and supervision. Fume cupboards against wall limits visibility of experiments by students. 0 WIFI enabled

Second means of escape through chemical store/prep room.

Narrow door does not meet current requirements. Access by way of poor quality lift opening directly into Lab 2 Lab 4 L414 0/1

Room area below norm. 1

No blackout provision limits experiments. Mechanical vent. 1

Poor relationship to Science staff facilities. 1

Fixed furniture layout restricts flexibility and supervision. Fume cupboards against wall limits visibility of experiments by students. 0 WIFI enabled

Second means of escape through chemical store/prep room.

Access by way of poor quality lift opening directly into Lab 2 19 Spaces Direct Impact on Education H & S/ Security Disabled Access Comments Type Category Unique Room Ref Room Designation Code Size/Shape Environment Location Fixed Furniture
ICT Infrastructure A B C D High Medium Low Yes No Prep 4/5 L416 0 1 Poor ventilation 0 0 0

Lab 3 and 4 second means of escape is through the prep area, potentially impeded by furniture and equipment.

Room layout makes use and access difficult. Lab 5 L420 0/1

Room area marginal. 1

No blackout provision limits experiments. Mechanical vent. 1

Poor relationship to Science staff facilities. 1

Fixed furniture layout restricts flexibility and supervision. 0 WIFI enabled

Second means of escape through chemical store/prep room.

Access by way of poor quality lift opening directly into Lab 2 at far end of science ‘string’ of rooms Lab 6 L442 0/1

Room area marginal. 1

No blackout provision limits experiments. Mechanical ventilation. 1

Poor relationship to Science staff facilities. 1

Fixed furniture layout restricts flexibility and supervision. Lack of storage 0 WIFI enabled

Second means of escape through chemical store/prep room.

Access by way of poor quality lift opening directly into Lab 2 then lengthy narrow corridor. 20 Spaces Direct Impact on Education H & S/ Security Disabled Access Comments Type Category Unique Room Ref Room Designation Code Size/Shape Environment Location Fixed Furniture ICT Infrastructure A B C D High Medium Low Yes No Prep 6/7 L443A 0 1 Poor ventilation 0 0 0

Door widths and layout make use and access difficult.

Lab 6 and 7 second means of escape for each classroom is through the prep area and adjoining classroom, potentially impeded by furniture and equipment.
Lab 7 L443 1

Room area below norm.
1

No blackout provision limits e

[Response truncated — full text is 208,593 characters]